Models For Outdoor Installation - Beretta IDRABAGNO Lx 11 Manual Del Instalador

Ocultar thumbs Ver también para IDRABAGNO Lx 11:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 63
E
D
C
flue gases pipe
A
suction line pipe
B
C
rubber rose
D
terminal
seat for rose
E
- seal the gap between the 100 Ø pipe and the hole in the wall with ce-
ment-based mortar, positioning a piece of paper so that the tube does
not remain fixed to the wall itself, so as to facilitate subsequent disas-
sembly. Place the appliance in the chosen position, with reference to
the measurements indicated in this instruction booklet in the "Func-
tional elements of the appliance / Max. dimensions and connections"
section.

3.3.2 Models for outdoor installation

The appliance has been designed only for installation outdoors in an area
that is partly covered. For this reason it must be installed in the open,
outdoors with natural aeration and ventilation, without stagnant zones for
combustion products, which should be rapidly dispersed by means of nat-
ural convection or by the wind.
The discharge outlet of the appliance should be free of obstructions, ob-
jects or bodies that could prevent it from expelling the flue gases correctly
and protected from an contacts during or after operation: it is possible it
overheats and cause burns.
Fig. 10: example of an INCORRECT evacuation of the products of the
combustion inside a balcony closed on five sides.
When the appliance is being installed the minimum distances of the dis-
charge/suction line must comply with current local legislation, having re-
gard for any other appliances installed, openings, architectonic elements,
and boundaries.
Positioning the terminal
B
Under a window
Next to a window
Under an aeration/purging open-
Next to an aeration/purging
Vertical distance between two
discharge terminals
A
Horizontally adjacent to a dis-
charge terminal
Under a balcony
Beside a balcony
From the ground or from another
From piping either vertical or
horizontal discharges (**)
Under the eaves
Fig. 9
Corner/recess/wall of the building
For type A appliances the minimum distance coincides with the cen-
(*)
tre of the outlet section for combustion products going into the air.
(**)
When positioning the appliance distances of not less than 500
mm must be adopted from materials sensitive to the action of the
combustion products (for example, plastic eaves and drainpipes,
protruding wood elements, etc.); for smaller distances use suitable
screening with regard to said materials.
b
For the minimum distances from combustible materials, see what
is reported in Fig. 12
Fig. 10
Position
A1
A2
B1
ing
B2
opening
C1
C2
D1
D2
E
walkway
F
G
H
ENGLISH
Minimum distances
(mm) (*)
Appliances over
16kW up to 35kW
600
400
600
600
1.500
1.000
300
1.000
2.200
300
300
300
Fig. 11
Fig. 12
29