PROHEAT II SERIES · HEAT PUMP AIR/WATER SYSTEM
V5
V4-V5: Adjustment valves
V4
SIPHON
Installation example of the Proheat II INDOOR equipment with centrifugal fan for indoor
installation only:
It is necessary to make the duct network so that the air collected by the machine to operate
the refrigeration circuit, never return to the machine, and must be expelled to the street. The
machine must be located exclusively inside.
In this example of installation, it can be seen that the technical room is perfectly ventilated
through a grid of sufficient size to guarantee the correct flow of air through the evaporator. And
that the driving air is driven outside.
If the distance between the machine and the outside air is too high, a duct can be connected
directly to the evaporator inlet, as long as the nominal air flow of the equipment is
guaranteed. The limit of loss of load of these models Indoor is 120 Pa, and if this value is not
respected, the heat pump can be damaged. For greater load losses available, consult Fluidra
Comercial.