PROHEAT II SERIES · HEAT PUMP AIR/WATER SYSTEM
temperature is lower than the "Setpoint temperature". The machine starts heating when the
probe temperature is lower than the "Temperature setpoint - Auto mode temperature
differential" and it stops heating when the temperature is higher than the "Setpoint
temperature".
6.4.2.
HEAT MODE
Start-up process:
Start-up conditions: Water intake temperature < (Setpoint temperature - Temperature
differential); and the Compressor stop time ≥ Compressor delay time.
6.4.3. COOL MODE (CHILLER MODELS)
Start-up process:
Start-up conditions: Water intake temperature < (Setpoint temperature + Temperature
differential); and the Compressor stop time ≥ Compressor delay time