AERMEC Novatherm pCO3 Manual De Uso página 37

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

ANALOGUE INPUTS
N
Air / water units type 00 / 01
B1 P.A.
Circuit high pressure transducers
B2 P.B.
Low pressure circuit transducer
Temperature probe inlet water
(MASTER) Evaporator common
B3 TIA (TUAC)
outlet water temperature probe
(SLAVE !)
Compressor discharge tempera-
B4 TGP
ture probe
B5 TUA
Output water temperature probe
Daikin Modulating capacity
control: Outside air temperature
probe
B6 TAE SUWH
Bitzer e Daikin Step cap. control:
Amperometric transformer input
Master: multifunctional input
B7 SUR
Slave: Recovery outlet tempera-
ture probe
Evaporator gas temperature
B8 TEV
probe
Daikin Modulating capacity con-
trol: Compressor potentiometer
B9 TAE SUWH
B10 TL SIWH
Liquid temperature probe
Recovery inlet temperature
B1 EXP SIR SFC
probe Inlet probe Free-cooling
coil inlet probe (Glycol free)
Recovery outlet temperature
B2 EXP SUR SFC2
probe Free-cooling coil outlet
probe (Glycol free)
Intermediate exchanger water
B3 EXP SRU
inlet probe (Glycol free)
B4 EXP
Not used
Bitzer e Daikin Step cap. control:
Outside air temperature probe
Water / water units type 03
/ 04
Circuit high pressure transducers
Low pressure circuit transducer
Temperature probe inlet
water (MASTER) Evaporator
common outlet water tem-
perature probe (SLAVE !)
Compressor discharge tem-
perature probe
Evaporator outlet water
temperature probe
Daikin Modulating capacity
control Condenser outlet
water temperature probe
Bitzer e Daikin Step cap. control:
Amperometric transformer
input
Master: multifunctional input
Slave: Recovery outlet tem-
perature probe
Evaporator gas temperature
probe
Daikin Modulating capacity
control Compressor poten-
tiometer
Bitzer e Daikin Step cap.
control: Condenser output
water temperature probe
Condenser inlet water tem-
perature probe (MASTER)
Condenser common outlet
water temperature probe
(SLAVE !)
-
Free-cooling coil outlet
probe (Glycol free)
Intermediate exchanger wa-
ter inlet probe (Glycol free)
Not used
WF-WSA-WSB-WSH UNITS
NOTES
Probe type 4-20 mA
Range 0-30 bar
Probe type 4-20 mA
Range 0-10 bar
Probe type NTC 10k Carel -
Only on master -
(Only on Slave1)
Probe PT1000
Probe type NTC 10k
Probe type NTC 10k In case of
use as transformer input do not
enable analogue input B6
Probe type NTC 10k In case of
use as multifunctional input do
not enable analogue input B7
Probe type NTC 10k
Probe type NTC 10k In case of
use as potentiometer do not
enable analogue input B9
Probe type NTC 10k
Probe type NTC 10k
On expansion
Probe type NTC 10k
on expansion
Probe type NTC 10k
On expansion
Probe type NTC 10k
On expansion
37

Publicidad

Tabla de contenido
loading

Tabla de contenido