CODE
AL62
Alarm unit 2 not connected: alarm if the card with address 2 does not communicate
AL63
Alarm unit 3 not connected: alarm if the card with address 3 does not communicate
AL64
Alarm unit 4 not connected: alarm if the card with address 4 does not communicate
Alarm anti-freeze evaporator gas: alarmif the evaporator gas antifreeze
AL75
temperature < setpoint
High pressure alarm motor condenser on models 02 and 03: alarm
AL80
if high pressure > setpoint for a predetermined time
Low pressure alarm from transducer not bypassed: alarm if low pressure < setpoint
AL85
if alarm enabled from menu and transducer enabled
Alarm for missing antifreeze probe. If not a motor condenser and there is no water probe,
AL90
alarm not enabled on circuit evaporator
AL91
Alarm condenser flow switch If in heating mode If models 03/04 ID15 open
Alarm condenser antifreeze If models 03/04
AL92
If condenser output temperature B9 < setpoint
AL93
Alarm electronic expansion valve If Digital Demand not enabled. ID16 open
AL100
The compressor works outside envelope (out of range)
AL101
inverter alarm
AL102
Overcurrent alarm
AL103
Supply voltage too high compressor
Too high temperature of the inverter
AL104
Check valve liquid and / or refrigerant charge
The valve is activated when the oil exceeds 100 ° C, and turns off when it falls below 95 ° C
AL105
Supply voltage too low compressor
AL106
Phase failure or power imbalance between phases
AL107
Inverter hardware fault
AL108
Fault inverter temperature sensors Check engine oil sensor and sensor
AL109
Alarm hardware configuration incorrect
AL110
Alarm software configuration incorrect
AL111
Alarm parameters inverter incorrect
AL112
Motor winding temperature exceeds the limits
AL113
Motor overload alarm
AL115
absence phase
High temperature oil (check oil resistance) Warning if greater 115 ° C
AL116
Fault if greater 120 ° C alarm reset if less than 105 ° C
AL117
Low oil: Check oil level and filters, check the oil level sensor
Warns that you are asking the ignition compressor before it has passed the minimum time
AL118
between two start. It occurs only at the level of Warning
AL119
Il compressore lavora fuori envelope (fuori campo di lavoro)
AL120
The compressor works outside envelope (out of range)
AL121
Serial communication alarm
40
DESCRIPTION
DIGITAL INPUT
RESET
pCO
CARD
ALARM(S)
3
-
-
-
-
-
-
-
ID15 open
-
ID16 open
MANUAL