INSTALLATION REqUIREMENTS
vENTIlATION
WARNING: The range should have proper ventilation in order to keep the unit operating properly and maintain
the temperature of immediate surroundings within safe limits. Check your local building codes as they may vary
from the general rules outlined in this guide. It is recommended that a hood be installed above the range that
is rated no less than 400 CFM. This will provide adequate ventilation for this range. Mounting distance of your
ventilation is outlined by the manufacturer of your hood.
To avoid damage to your cabinets, check with your builder or cabinet supplier to make sure that the materials
used will not discolor, delaminate or sustain other damage. This oven has been designed in accordance with the
requirements of Ul and CSA International and complies with the maximum allowable wood cabinet temperatures
of 200°F.
•
Observe all governing codes and ordinances. DO NOT obstruct flow of combustion and ventilation air.
•
It is the installer's responsibility to comply with installation clearances specified on the model/serial rating
plate.
•
The range should be located for convenient use in the kitchen.
•
Recessed installations must provide complete enclosure of the sides and rear of the range.
•
To eliminate the risk of burns or fire by reaching over heated surface units, cabinet storage space located
above the surface units should be avoided. If cabinet storage is to be provided, the risk can be reduced by
installing a range hood or microwave hood combination with minimum 400 CFM that projects horizontally
a minimum of 5" (127 mm) beyond the bottom of the cabinets.
•
If a range hood is installed above the appliance, maintain a 30" minimum clearance between cooking
surface and bottom of range hood. The range hood must be connected directly to flues or to the outside.
•
Avoid placing cabinetry directly above the appliance when possible. If cabinetry is used above the cooking
surface, use cabinets no more than 13" deep. Make sure the wall coverings, countertop and cabinets around
the appliance can withstand heat up to 200°F generated by the appliance.
•
Cabinet opening dimensions that are shown in
must be used. Given dimensions are
•
Working areas adjacent to the range should have 18"
(457 mm) minimum clearance between countertop and
cabinet bottom.
•
All openings in the wall or floor where range is to be
installed must be sealed.
•
Contact a qualified floor covering installer to check that the
floor covering can withstand at least 200°F.
•
Use an insulated pad or ¼" (64 mm) plywood under
range if installing range over carpeting.
•
The floor anti-tip bracket must be installed. To install
the anti-tip bracket shipped with the range, refer to
"Anti-Tip bracket" section on page 12.
•
Grounded electrical supply is required. Refer to
"Electrical Connection" section on page 13.
Figure 3
minimum clearances.
10
13.0" (589 mm) Max
30.0" (762 mm)
Figure 3
18.0"
(457 mm)