EVO
winter switching cannot be set on "Auto on water
temp.";
it is only possible to set summer/winter switching on
"Auto on air temp." if there is an electric heater or if the
unit has 4-pipes;
If SUMMER/WINTER switching is set on "Auto on water
temp." it is not possible to use a 2-way valve. The water
probe must be installed on a point in the hydraulic
circuit with minimum circulation.
CONFIGURABLE DIGITAL OUTPUT
The board has a digital output (identified by O7 on the electrical
diagram) and its status is linked to one of the operating statuses
of the unit reported in the list below:
Operating mode
Cooling or heating request
Cooling request
Heating request
ON/OFF status of the unit
Alarm installed
External dehumidification signal
External humidification signal
High room temperature
Low room temperature
No water consent to heating
No water consent to cooling
and selectable from the "DOUT Configuration" configuration
parameter. It is also possible to choose, using the next "Digital
output logic" parameter setting, whether the status of the relay
needs to follow the logic NO (Normally Open) or NC (Normally
Closed).
FC66003554
Rev 00
Controller for units
USER MANUAL
IT IS strictly forbidden to reproduce this manual, even partially
STAND-BY MODE
If no operation is performed on the user unit keyboard for 30
seconds the main screen goes into stand-by mode, which
can differ based on the settings of the "Stand-by Mode"
parameter, accordingly:
Stand-by mode = Off: the display goes completely
black;
Stand-by mode = Clock: the display goes partly black
and the current time and date are shown;
Stand-by Mode = Temperature: the display goes partly
black and the room temperature and any humidity are
shown, if the probe is installed.