Post ventilation due to the heater switching off:
maintained until the end of the set time, even if the
operation mode is changed. During post-ventilation
water consent coincides with consent required for
ventilation.
ELECTRICAL HEATER
SWITCHING IT ON
If it has been preventively included by the configuration
parameter and use is enabled by the setup parameter, the
electrical heater is used when the thermostats requires it,
based on the room temperature:
n
et-
Switching it on entails forced ventilation.
WATER CONSENT
Consent to switch on the heater depends on water
temperature control. The following is the relative consent
logic:
HEATING
.
This enabling signal will not be given if the water probe is not
included or is disconnected.
FC66003554
Rev 00
t. aria
et
o
t. a
a
.
IT IS strictly forbidden to reproduce this manual, even partially
Controller for units
ECONOMY
If it has been preventively included by the configuration
parameter and use is enabled by the setup parameter, the
Economy function will correct the setpoint by 2.5°C and
force operation at the minimum available seed to reduce unit
operation.
Cooling: set + 2.5°C
Heating: set – 2.5°C
MINIMUM TEMPERATURE CONTROL
If it has been preventively included by the configuration
parameter and use is enabled by the setup parameter, when
the thermostat is off, this logic avoids the room temperature
from dropping below a settable threshold ("Minimum
temperature control SET"), forcing the unit to heating mode
for the required amount of time.
If the electrical heater is present, it will be used only if it was
previously selected as a resource in the Heating mode.
SWITCHING IT ON
If this control is selected, the terminal will turn on if the room
temperature falls below 9°C:
Once the temperature returns above 10°C, the thermostat
will go back Off.
Pressing OFF on the digital input will deactivate
this logic.