Technical data
Power circuitry
Rated voltage U
N
Rated power DC
Rated power AC
Residual ripple U
SS
Rated frequency
Operating voltage range
Protection for control circuit supply
Control circuit
Outputs S13, S23
Rated output voltage S13, S23
No-load voltage AC device
Output current
Short-circuit-proof / current limiting
Inputs S14/S33, S22, S24, S34, S35
Input voltage range (for external supply, only on DC devices)
Rated current / peak current S14/S33, S22, S24
Rated current / peak current S34, S35
Times
Permissible test pulse time t
/ test frequency
TP
Operate time t
S34
A1
Operate time t
S35
A2
Operate time t
A3
Min. ON time t
S34, S35
M
Synchronous time t
CH1 before CH2
S
Recovery time t
W
Release time t
K1, K2
R
Output circuit
Enabling paths
Contact equipment
Rated switching voltage U
n
Max. continuous current I
per current path
n
fuse
Max. total current for all current paths
Utilization category according to DIN EN 60947-5-1
Mechanical service life
General data
Clearance/creepage distance between circuits
Overvoltage category
Rated impulse withstand level
Contamination level of device: inside / outside
Rated voltage
Power-frequency test voltage
Protection class to DIN EN 60529 housing / terminals
Ambient / storage temperature
Climatic application class
Weight
Terminals and connection data
Single-core or finely stranded
Finely stranded with wire-end ferrule acc. to DIN 46228
AWG
Max. tightening torque
Stripping length
6
DC device
AC device
AC/DC 24 V, AC 115 - 120 V, AC 230 V
2.0 W
2.6 W / 3.2 VA
2.4 V
50 ... 60 Hz
0.85 ... 1.1 x U
N
Short-circuit-proof (DC devices: PTC thermistor / AC devices: short-circuit-proof
transformer)
DC 22 V
< 40 V
100 mA
Yes / No
DC 17.4 V to DC 26.4 V
40 mA / 100 mA
5 mA / 50 mA
1000 s / 10 s
-1
20 ms to 40 ms
200 ms to 600 ms
100 ms to 400 ms
> 80 ms
approx. 200 ms
100 ms
< 25 ms
3 NO contacts, positively driven
AC 230 V
6 A
max. 6 A operating class gG / fuse integral < 100 A²s
9 A²
AC-15: Ue 230 V, Ie 3 A
DC-13: Ue 24 V, Ie 2,5 A
7
10
switching cycles
DIN EN 60664-1
IV
4 kV
2 / 3
300 V
2 kV
IP 40 / IP 20
-25 ... +55 °C / -25 ... +75 °C
H V G to DIN 40040: 04:87
0.21 kg
0.25 kg
screw-type terminals
1 × 0.2–2.5 mm² / 2 × 0.2–1,0 mm²
1 × 0.25–2.5 mm² / 2 × 0.25–1,0 mm²
26–14
0.5–0.6 Nm (4–5 lbf in)
spring-type terminals
1 × 0,2–1,5 mm²
1 × 0,25–1,5 mm²
(trapezoid crimping)
24–16
—
max. 7 mm