74 01
Safety edge 2 setup
00
NOT PRESENT
01
SWITCH, reverses while closing only
02
8k2, reverses while closing only
03
SWITCH, always reverses
04
8k2, always reverses
75 00
Encoder setup
00
NEITHER PRESENT
01
BOTH OPTICAL (8 pulses per revolution)
02
BOTH MAGNETIC (1 pulse per revolution)
Where no encoder is fitted, the gate is controlled based on operating time.
Most ROGER motors with encoders use optical encoders; only the E30 series uses magnetic encoders (if you
are in any doubt, read the instructions carefully or get in touch with our support team).
76 00
Radio channel 1 setup
77 01
Radio channel 2 setup
00
PP (STEP-BY-STEP)
01
PEDESTRIAN
02
OPEN
03
CLOSE
04
STOP
05
COURTESY the relay is controlled by radio only; normal operation is disabled
STEP-BY-STEP COURTESY (switches light on-off) the relay is controlled by radio only; normal
06
operation is disabled
07
FLASHING LIGHT the relay is controlled by radio only; normal operation is disabled
STEP-BY-STEP FLASHING LIGHT (switches light on-off) the relay is controlled by radio only;
08
normal operation is disabled
78 00
Flashing light setup
00
STEADILY LIT (flashing light's own circuit responsible for flashing)
01
slow flashing switched on
02
slow flashing switched on while opening; fast flashing switched on while closing
7-
NOTE: parameter
The flashing light comes on when the gate is moving; it can be set to work continuously (where flashing
lights have a built-in flashing circuit on a timer) or can be controlled directly by the control unit (for flashing
lights fitted with a simple light bulb).
79 60
Courtesy light time
00
OFF (disabled)
01
PULSE MODE (switched on for short time every time the gate starts to move)
02
on for duration of cycle
03
90
how long, in SECONDS, the light stays on after the cycle has ended
-
92
99
from 2 to 9 minutes after the cycle has ended
-
in easy setup mode