Control Electronics Power Wiring

Your relay cabinet requires a specific power circuit for the control electronics.
Leviton recommends that this power circuit be dedicated specifically and used
only for power to the control electronics.
NOTE:
If any Emergency Circuits are fed or controlled from this panel, it must be
located electrically where fed from a UPS, generator, or other guaranteed
source of power during emergency and power outage situations.
To connect your relay cabinet's control electronics to power, please follow these steps:
Step 1:
Connect the relay cabinet to the circuit panel using conduit.
Step 2:
Remove all cuttings and dirt.
Step 3:
Run a dedicated circuit from the circuit panel or distribution panel to the relay
panel for the control electronics. Make sure the power is OFF at the breaker.
Step 4:
Wire the circuit as shown in the following figure:
Multi-Tap Transformer
Dedicated Circuit
24 & 48 Relay Cabinets Control Electronics Power Wiring
NOTE:
The transformer leads can be found in the lower right corner on the 8 cabinet
and underneath the control module on the right hand side of the 24 and 48
cabinet.
NOTE:
The 48 cabinet has two sets of leads which can be connected in parallel to
the same dedicated circuit.
NOTE:
Branch circuit wiring must be a minimum of 14 AWG.
Step 6:
Connect the circuit's ground wire to the relay cabinet.
Step 7:
Keep the circuit OFF until all wires are terminated, tested, and
double checked.
Cap off unused leads
with wire connectors
Neutral White
347V - Orange
277V - Brown
120V - Black
11