Detailed Confi guration Instructions
Default Confi guration
When shipped from the factory, the following basic settings are in place:
Rate Mode Operation in % Units
Unipolar Output without Deadband
Decimal Point Display: XXX.X
Display Range: 0 - 100.0
Output Range: 0 - 100% of Applied Pot High Voltage
Signal Input 1 (S1) Mode: Force Output to 0% when Low
Signal Input 2 (S2) Mode: Force Output to 0% when Low
Alarm Output: Disabled
Resetting the Unit to Factory Defaults
The factory-default settings can be easily restored using either of two methods. Both methods require
the Program Enable jumper to be in the "On" position. The fi rst is to apply power to the unit with both
the Enter and Down buttons pressed for 3 seconds. The second is to change the value of parameter
95 to 5.
JP1 (Program Enable Jumper)
The JP1 jumper is located under the dust cover on the back end of the upper board. When the jumper
is set to the "Off" position, all programming features are locked out to the front panel user. When the
jumper is in the "On" position, the programming parameters are open to change. JP1 is shipped from
the factory set in the "On" position.