To fill your engine with oil:
Follow the synthetic oil grade recommendation and oil fill
instructions given in the engine operator's manual.
notice
Any attempt to crank or start the engine before it has
been properly serviced with the recommended oil will
result in equipment failure.
Refer to Maintenance and engine manual for oil
fill information.
Damage to equipment resulting from failure to follow this
instruction will void engine and generator warranty.
Air Filter
The engine for this generator is equipped with a UL
recognized air filter. When servicing the air filter, follow the
instructions given in the engine operators manual. Replace
ONLY with same type UL recognized air filter, P/N 79063.

Battery

Servicing of batteries is to be performed or supervised
by personnel knowledgeable of batteries and the
required precautions. Keep unauthorized personnel away
from batteries.
WARNING
Battery posts, terminals and related
accessories contain lead and lead compounds
- chemicals known to the State of California
to cause cancer and reproductive harm. Wash
hands after handling.
Charging the Battery
If it is necessary to charge the battery, proceed as follows:
1. Set generator's system switch to OFF.
. Remove 15 Amp fuse from control panel.
3. Disconnect negative battery cable from negative battery
terminal (indicated by NEGATIVE, NEG, or (-).
notice
Failure to disconnect negative battery cable will result in
equipment failure.
DO NOT attempt to jump start the battery.
Damage to equipment resulting from failure to follow this
instruction will void warranty.
4. Charge battery with battery charger at  Amps until
battery holds 1 Volts.
NOTE: DO NOT exceed 13.7 volts charging.
18
WARNING
Storage batteries give off explosive hydrogen
gas during recharging.
Slightest spark will ignite hydrogen and
cause explosion.
Battery electrolyte fluid contains acid and is
extremely caustic.
Contact with battery contents will cause severe
chemical burns.
A battery presents a risk of electrical shock and
high short circuit current.
DO NOT dispose of battery in a fire. Recycle battery.
DO NOT allow any open flame, spark, heat, or lit cigarette
during and for several minutes after charging a battery.
DO NOT open or mutilate the battery.
Wear protective goggles, rubber apron, rubber boots and
rubber gloves.
Remove watches, rings, or other metal objects.
Use tools with insulated handles.
NOTE: With the battery installed and utility power available
to the transfer switch, the battery receives a trickle charge
whenever the engine is not running. It may take up to
7 hours to fully charge a battery with the trickle charge.
The trickle charge is not able to recharge a battery that is
completely discharged.
5. Connect negative battery cable to negative battery
terminal (indicated by NEGATIVE, NEG, or (-)).
6. Ensure hardware on both positive and negative battery
terminals is secure.
7. Reinstall 15 Amp fuse in control panel.
CAuTION
Installing the 15A fuse could cause the engine
to start.
DO NOT install this fuse until all plumbing and wiring has
been completed and inspected.
8. Set generator's system switch to AUTO.
9. Reset exercise timer. See Setting Exercise Timer.