8.6.2 Connection mode of pipe
The water inlet and outlet pipes are installed and connected as shown in the following figures. Models 30 uses screwed
connection, while models 60 uses hoop connection (victaulic type). For the specifications of the water pipes and screw
thread, see the Table 8-7 below.
Table 8-7
Pipe connection methods
Model
MUENR-30-H9T and
Screwed connection
MUENR-30-H9T(K)
MUENR-60-H9T and
Hoop connection
MUENR-60-H9T(K)
(Victaulic)
8.6.3 Design of the store tank in the system
kW is the unit for cooling capacity and L is the unit for G, water flow in the formula counting the minimum water flow.
Comfortable air conditioner
G= cooling capacity×3.5L
Process cooling
G= cooling capacity×7.4L
In certain occasion (especially in manufacture cooling process), for conforming the system water content requirement,
it's necessary to mount a tank equipping with a cut-off baffle at the system to avoid water short-circuit, Please see
the following schemes:
Specifications of water pipe
Fig.8-20 connection mode of models 30
Fig.8-21 connection mode of models 60
84
Specifications of screw thread
DN40
DN50
Rc 1 1/4
/