Product Data - mundoclima MUC-W9 Serie Manual De Instalación Y Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

6.3 Product Data

Table 6-1
MODEL
Air flow volume(m
/h)
3
Cooling capacity(kW)(*)
Heating capacity(kW)(**)
Sound pressure(dB(A))(***)
Rated input(W)
Rated current(A)
Standard coil connections
Condensation drain pipe connection
Power supply
MODEL
Air flow volume(m
/h)
3
Cooling capacity(kW)(*)
Heating capacity(kW)(**)
Sound pressure(dB(A))(***)
Rated input(W)
Rated current(A)
Standard coil connections
Condensation drain pipe connection
Power supply
(*) Conditions: ambient temperature 27°C DB/19°C WB; water inlet temperature 7°C; water outlet temperature 12°C; high speed
(**) Conditions: ambient temperature 20°C DB/15°C WB; water inlet temperature 45°C; water outlet temperature 40°C; high
speed
(***) The sound pressure level in dB(A) indicates the value measured at 1 m away from an open air outlet.
Sound pressure level is below 70 dB.
MUC-05-W9
MUC-08-W9
255
400
1,50
2,35
1,57
2.60
34
15
0,18
0,20
G3/4
ODΦ18.5mm
220-240V~ 50Hz
MUC-16-W9
MUC-19-W9
790
1190
4.30
5.60
4.30
6.00
46
50
0.49
0.85
ODΦ18.5mm
220-240V~ 50Hz
46
MUC-11-W9
595
3.50
3.50
38
29
26
17
0.26
MUC-24-W9
1360
7.35
8.05
51
52
96
113
0.95
G3/4

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Muc-05-w9Muc-08-w9Muc-11-w9Muc-16-w9Muc-19-w9Muc-24-w9