English
All LEDs light up simultaneously for 2 sec.
Cause: Button lock active
Solution: Deactivate the button lock by simultaneously
pressing down the Manual Mode, Stop and Automatic
Mode buttons (for approx. 1 s).
All LEDs light up from right to left.
Cause: Incorrect phase sequence in mains connection
Solution: Swap over 2 phases in the switchgear's mains
connection
10.3. Fault memory
The switchgear has a fault memory. The last fault is stored reten-
tively in the fault memory.
Opening the fault memory
By pressing down the Stop and Automatic Mode buttons
simultaneously, the last fault is indicated by the corre-
sponding LED.
Deleting the fault memory
The fault memory is deleted by simultaneously pressing
and holding down (for approx. 1 s) the Manual Mode and
Stop buttons.
10.4. Further steps for troubleshooting
If the points listed here do not rectify the fault, contact Salmson
customer service. They can help you as follows:
• Telephone or written support from Salmson customer
service
• On-site support from Salmson customer service
• Inspection or repair of the switchgear at the factory
Please note that you may be charged for some services provided
by our Customer Service. For more details, please contact Salmson
customer service.
11.
Appendix
11.1. System impedance tables
System impedances for 1~230 V, 2-pole, direct starting
Power
System impedance
kW
ohms
1.5
0.4180
2.2
0.2790
1.5
0.3020
2.2
0.1650
1.5
0.2720
2.2
0.1480
System impedances for 3~400 V, 2-pole, direct starting
Power
System impedance
kW
ohms
2.2
0.2788
3.0
0.2000
System impedances for 3~400 V, 2-pole, direct starting
System impedances for 3~400 V, 4-pole, direct starting
11.2. Spare parts
Spare parts can be ordered from Salmson customer service. To
avoid return queries and incorrect orders, the serial and/or article
number must always be suppled.
Connections/h
6
6
24
24
30
30
Connections/h
6
6
37
Power
System impedance
kW
ohms
4.0
0.1559
2.2
0.2126
3.0
0.1292
4.0
0.0889
2.2
0.1915
3.0
0.1164
4.0
0.0801
Power
System impedance
kW
ohms
3.0
0.2090
4.0
0.1480
2.2
0.2330
3.0
0.1380
4.0
0.0830
2.2
0.2100
3.0
0.1240
4.0
0.0740
Subject to change without prior notice
Connections/h
6
24
24
24
30
30
30
Connections/h
6
6
24
24
24
30
30
30