Hydraulic System; Fuel Supply - Riello Burners RL 28 Instrucciones De Instalación, Funcionamiento Y Mantenimiento

Quemadores de gasóleo
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

7
10
9
6
7
6
+ H
RL 28
- H
Æ (mm)
(m)
8
10
+ 4,0
52
134
160
+ 3,0
46
119
160
+ 2,0
39
104
160
+ 1,0
33
89
160
+ 0,5
30
80
160
0
27
73
160
- 0,5
24
66
144
- 1,0
21
58
128
- 2,0
15
43
- 3,0
8
28
- 4,0
-
12
(A)
4
1
2 3
(B)
A
5
8
4
5
9
B
L (m)
RL 38
Æ (mm)
12
8
10
12
35
90
152
30
80
152
26
69
152
21
59
130
19
53
119
17
48
108
15
43
97
13
37
86
96
9
27
64
65
4
16
42
33
-
6
20
1
2
3
D3278
RL 50
Æ (mm)
10
12
14
63
144
150
55
127
150
48
111
150
40
94
150
37
86
150
33
78
150
29
70
133
25
62
118
17
45
88
10
29
58
-
12
28
D3279
7

HYDRAULIC SYSTEM

FUEL SUPPLY

Double-pipe circuit (A)
The burner is equipped with a self-priming pump
which is capable of feeding itself within the limits
listed in the table at the side.
The tank higer than the burner A
The distance "P" must not exceed 10 meters in
order to avoid subjecting the pump's seal to ex-
cessive strain; the distance "V" must not exceed
4 meters in order to permit pump self-priming
even when the tank is almost completely empty.
The tank lower than the burner B
Pump depression values higher than 0.45 bar
(35 cm Hg) must not be exceeded because at
higher levels gas is released from the fuel, the
pump starts making noise and its working life-
span decreases.
It is good practice to ensure that the return and
suction lines enter the burner from the same
height; in this way it will be less probable that the
suction line fails to prime or stops priming.
The loop circuit
A loop circuit consists of a loop of piping departing
from and returning to the tank with an auxiliary
pump that circulates the fuel under pressure. A
branch connection from the loop goes to feed the
burner. This circuit is extremely useful whenever
the burner pump does not succeed in self-priming
because the tank distance and/or height differ-
ence are higher than the values listed in the table.
Key (A)
H =
Pump/Foot valve height difference
L =
Piping length
Æ =
Inside pipe diameter
1 =
Burner
2 =
Pump
3 =
Filter
4 =
Manual on/off valve
5 =
Suction line
6 =
Foot valve
7 = Rapid closing manual valve remote con-
trolled (only Italy)
8 = On/off solenoid valve (only Italy)
9 =
Return line
10 = Check valve (only Italy)
HYDRAULIC CONNECTIONS (B)
The pumps are equipped with a by-pass that
connects return line with suction line. The pumps
are installed on the burner with the by-pass
closed by screw 6)(B)p.12.
It is therefore necessary to connect both hoses
to the pump.
The pump will break down immediately if it is run
with the return line closed and the bj-pass screw
inserted.
Remove the plugs from the suction and return
connections of the pump.
Insert the hose connections with the supplied
seals into the connections and screw them
down.
Take care that the hoses are not stretched or
twisted during installation.
Route the hoses through the holes in the plate,
preferably using those on the rh side, fig. (B):
unscrew the screws 1), now divide the insert
piece into its two parts 2) and 3) and remove the
thin diaphragm blocking the two passages 4).
Install the hoses where they cannot be stepped
on or come into contact with hot surfaces of the
boiler.
Now connect the other end of the hoses to the
supplied nipples, using two wrenches, one to
hold the nipple steady while using the other one
to turn the rotary union on the hose.