TECHNICAL DATA
MODEL
TYPE
OUTPUT
(1)
DELIVERY
(1)
FUEL
- Net calorific value
- Density
- Viscosity at 20 °C
OPERATION
NOZZLES
STANDARD APPLICATIONS
AMBIENT TEMPERATURE
COMBUSTION AIR TEMPERATURE
ELECTRICAL SUPPLY
ELECTRIC MOTOR
MOTOR CAPACITOR
IGNITION TRASFORMER
PUMP
delivery (at 20 bar)
pressure range
fuel temperature
ELECTRICAL POWER CONSUMPTION
ELECTRICAL PROTECTION
IN CONFORMITY WITH EEC DIRECTIVES
NOISE LEVELS
(2)
(1) Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m a.s.l.
(2) Sound pressure measured in manufacturers combustion laboratory, with burner operating on test boiler and at maximum rated output.
VARIANTS
Model
Code
3473232
RL 28
3473233
3474132
3474133
RL 38
3474332
3474333
3474632
RL 50
3474633
ACCESSORIES (optional):
•
STATUS (see page 16): code 3010321
•
DEGASSING UNIT
It may occur that a certain amount of air is contained in the light oil sucked up by the pump. This air may originate from the light oil itself as a
consequence of depressurization or air leaking past imperfect seals.
In double-pipe systems, the air returns to the tank from the return pipe; in single-pipe systems, the air remains in circulation causing pressure var-
iations in the pump and burner malfunctions.
For this reason, we advise installing a degassing unit near the burner in single-pipe installations.
Degassing units are provided in two versions:
CODE 3010054 without filter
CODE 3010055 with filter
Degassing unit characteristics
• Burner delivery
• Light oil pressure
• Ambient temperature
• Light oil temperature
• Attachment connectors
2nd stage
kW
Mcal/h
kg/h
1st stage
kW
Mcal/h
kg/h
kWh/kg
Mcal/kg
kg/dm
2
/s max 6 (1,5 °E - 6 cSt)
mm
number
°C
°C max
V
Hz
rpm
W
V
A
µF/V
V1 - V2
I1 - I2
kg/h
bar
° C max
W max
dBA
Electrical
Blast tube
supply
lenght mm
single-phase
216
single-phase
351
single-phase
216
single-phase
351
three-phase
216
three-phase
351
three-phase
216
three-phase
351
: 80 kg/h max
: 0,7 bar max
: 40 °C max
: 40 °C max
: 1/4 inch
RL 28
RL 38
652 T1
653 T1
166 - 332
237 - 450
143 - 286
204 - 387
14 - 28
20 - 38
95 - 166
118 - 237
82 - 143
102 - 204
8 - 14
10 - 20
LIGHT OIL
11,8
10,2 (10.200 kcal/kg)
3
0,82 - 0,85
• Intermittent (min. 1 stop in 24 hours).
• Two-stage (high and low flame) and single-stage (all - nothing).
2
Boilers: water, steam, diathermic oil
0 - 40
60
230 ~ +/-10%
50 - single-phase
2800
300
220 - 240
220 - 240
2,4
12,5/450
16/450
230 V - 2 x 5 kV
1,9 A - 30 mA
45
10 - 18
4 - 18
60
370
IP 44
89/336 - 73/23 - 92/42 - 98/37
68,0
2
RL 38
653 T1
237 - 450
204 - 387
20 - 38
118 - 237
102 - 204
10 - 20
230 - 400 with neutral ~ +/-10%
50 - three-phase
2800
2800
420
450
220/240 - 380/415
2,8
2,0 - 1,2
67
67
4 - 18
60
60
600
560
70,0
70,0
RL 50
654 T1
296 - 593
255 - 510
25 - 50
148 - 296
127 - 255
12,5 - 25
2800
650
220/240 - 380/415
3,0 - 1,7
88
4 - 18
60
750
75,0