Indoor Unit Drain Piping; Drain Piping; Drain Test - LG MS15SQNB0 Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 57
THE INDOOR UNIT INSTALLATION
18

Indoor unit drain piping

- Drain piping must have down-slope (1/50 to
1/100): be sure not to provide up-and-down
slope to prevent reversal flow.
- During drain piping connection, be careful
not to exert extra force on the drain port on
the indoor unit.
- Remove the rubber stopple before connect-
ing drain hose.
- Hook on the bracket after connecting the
drain hose as below.

Drain piping

- The drain hose should point downward for
easy drain flow.
Bracket
Drain hose
Downward
slope
- Do not make drain piping like the following.
Do not raise
Water
leakage
Tip of drain
hose dipped
in water
Water
leakage
Ditch
- Be sure to execute heat insulation on the
drain piping.
Heat insulation material: Polyethylene foam
with thickness more than 8 mm.

Drain test

Use the following procedure to test the drain
pump operation:
- Set the air direction louvers up-and-down to
the position(horizontally) by hand.
- Pour a glass of water on the evaporator
using a kettle.
- Ensure the water flows through the drain
hose of the indoor unit without any leakage
and goes out the drain exit.
Accumulated
drain water
Air
Water
Waving
leakage
Less than
50 mm gap

Publicidad

Tabla de contenido
loading

Tabla de contenido