CONCRETE FLOOR INSTALLATION (FIGURE 3)
1. Mark the location of the mounting holes using the OIP Frame Drill Template (Figure 2, Item 3) as a
guide
2. Use 5/8" diameter ½" x 13 thread Pin-Drive Anchors with minimum tension strength of 4,000 lbs.
and minimum shear strength of 4,900 lbs (figure 3 - item 13)
3. Drill holes in floor per anchor manufacturer recommended instructions
4. Install anchors per manufacturer recommended instructions
5. Place OIP Upright over threaded rods with the open side facing the opposite upright
CAUTION - Make sure the OIP Upright is supported while being mounted to the floor.
6. Use ½" x 13 nuts, locking washer and fender washers, loosely secure upright foot to the anchor.
(figure 3 - items 14, 15 and 16)
RAISED FLOOR INSTALLATION (FIGURE 4)
1. Mark the location of the mounting holes for both raised floor panels and concrete floor using the OIP Frame
Drill Template (Figure 2, Item 3) as a guide
2. Use 5/8" diameter ½" x 13 thread Hex Head Anchors with minimum tension strength of 7,500 lbs. and
minimum shear strength of 11,900 lbs. in the concrete floor (figure 4 – item 17)
3. Drill holes as required in raised floor panel
4. Drill holes in floor per anchor manufacturer recommended instructions
5. Install anchors per manufacturer recommended instructions
6. Remove bolt from anchors
7. Replace floor panels
8. Install ½" threaded rods through floor panels (figure 4 – item 18)
9. Install ½" threaded rods through sub-floor mounting plate (figure 4 – items 4 and 18)
10. Install nut, locking washer and fender washer on threaded rods (figure 4 – items 14, 15 and 16)
11. Use ½" x 13 jamming nuts to install threaded rods in anchors
12. Torque threaded rod to anchor manufacturer recommended value
13. Place OIP Upright over threaded rods with the open side facing the opposite upright and loosely secure with
appropriate hardware based on concrete or raised floor mounting (figure 4 – items 7 and 18)
CAUTION - Make sure the OIP Upright is supported while being mounted to the floor.
14. Install nut, locking washer and fender washer to secure upright foot to the threaded rod (figure 4 – items 14,
15 and 16)
15. Adjust under floor and above floor nut assemblies as necessary to assure level of raised floor panels
16. Tighten under floor and above floor nut assemblies as necessary to assure sufficient clamping of upright
foot and sub-floor plate to floor panels
17. Torque all under floor mounting hardware to manufacturer recommended value
PK-93767-10-02-0B