Remove The DC Sensor
Cap/Capuchon/Tapa
DC Sensor Connector
Connecteur capteur c.c.
Conector del sensor de CC
Perform the following steps to remove the DC sensor and battery:
Close the control stop valve.
Using a 3/32" hex wrench, remove the setscrew from the valve cap and remove
the cap.
Disconnect the DC sensor connector to the solenoid by grasping each side of the
connector pair and pulling apart. Do not separate the connector pair by pulling on
the wires.
Remove the wedge clip that holds the DC sensor in place inside the cap.
Turn the cap over and slide the sensor into your hand.
If replacing the DC sensor, discard the old DC sensor and batteries in accordance
with any applicable codes.
Reinstall the battery holder assembly.
Retirer le capteur DC
Procéder aux étapes suivantes pour retirer le capteur DC et la pile:
Fermer la valve de la soupape de contrôle.
Utiliser une clé hexagonale de 3/32 po pour retirer la vis de retenue du capuchon
de la valve et retirer le capuchon.
Déconnecter le connecteur du capteur DC au solénoïde en saisissant chaque côté
de paire de connecteurs et en séparant. Ne pas séparer le connecteur en tirant sur
les câbles.
Retirer le clip de rebord qui maintient le capteur c.c. en place à l'intérieur du
capuchon.
Retourner le capuchon et glisser le capteur dans la main.
Lors du remplacement du capteur DC, jeter l'ancien capteur DC et les batteries en
suivant les codes applicables.
Réinstaller l'ensemble de compartiment à piles.
1117785-2-C
Setscrew
Vis de retenue
Tornillo de fijación
DC Sensor
Capteur c.c.
Sensor de CC
Wedge Clip
Clip à rebord
Clip acuñado