Control Techniques UNIDRIVE SP1201 Guía Rápida página 46

Ocultar thumbs Ver también para UNIDRIVE SP1201:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Safety
Product
Mechanical
Information
Information
Installation
Trip
SMARTCARD trip: The data blocks on the SMARTCARD are not compatible with this
C.Prod
product
Erase all data on the SMARTCARD by setting Pr xx.00 to 9999 and pressing the red
175
button
Replace SMARTCARD
C.rdo
SMARTCARD trip: SMARTCARD has the Read Only bit set
Enter 9777 in Pr xx.00 to allow SMARTCARD Read / Write access
181
Ensure card is not writing to data locations 500 to 999
SMARTCARD trip: The voltage and/or current rating of the source and destination drives
C.rtg
are different
Drive rating dependent parameters (parameters with the RA coding) are likely to have different
values and ranges with drives of different voltage and current ratings. Parameters with this
attribute will not be transferred to the destination drive by SMARTCARDs when the rating of the
destination drive is different from the source drive and the file is a parameter file. However, with
software V01.09.00 and later dDrive rating dependent parameters will be transferred if only the
current rating is different and the file is a differences from default type file.
Press the red
Drive rating parameters are:
Parameter
4.05/6/7, 21.27/8/9
186
5.07, 21.07
5.09, 21.09
5.10, 21.10
5.17, 21.12
5.23, 21.13
5.24, 21.14
5.25, 21.24
The above parameters will be set to their default values.
C.TyP
SMARTCARD trip: SMARTCARD parameter set not compatible with drive
Press the reset button
187
Ensure destination drive type is the same as the source parameter file drive type
dESt
Two or more parameters are writing to the same destination parameter
199
Set Pr xx.00 = 12001 check all visible parameters in the menus for duplication
EEPROM data corrupted - Drive mode becomes open loop and serial comms will timeout
EEF
with remote keypad on the drive RS485 comms port.
31
This trip can only be cleared by loading default parameters and saving parameters
Enc1
Drive encoder trip: Encoder power supply overload
Check encoder power supply wiring and encoder current requirement
189
Maximum current = 200mA @ 15V, or 300mA @ 8V and 5V
Enc2
Drive encoder trip: Wire break (Drive encoder terminals 1 & 2, 3 & 4, 5 & 6)
Check cable continuity
Check wiring of feedback signals is correct
Check encoder power is set correctly
190
Replace feedback device
If wire break detection on the main drive encoder input is not required, set Pr 3.40 = 0 to disable
the Enc2 trip
46
Electrical
Getting
Menu 0
Installation
Started
reset button
2.08
Standard ramp voltage
Current limits
4.24
User current maximum scaling
Motor rated current
Motor rated voltage
Rated power factor
Stator resistance
5.18
Switching frequency
Voltage offset
Transient inductance
Stator inductance
6.06
DC injection braking current
6.48
Mains loss ride through detection level
www.controltechniques.com
Running
Advanced
Diagnostics
the motor
parameters
Diagnosis
Function
Unidrive SP Short Form Guide
UL Listing
Appendix
Information
reset
Issue Number: 2

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Unidrive sp5402

Tabla de contenido