ENGLISH
In case of chimney fi re:
•
Close all hatches and vents.
•
Keep the fi rebox door closed.
•
Check the loft and cellar for smoke.
•
Call the fi re service.
•
Before use after a fi re an expert must check the fi replace
and the chimney in order to ensure that it is fully functional.
4.0 Installation
N.B. Check that the fi replace is free of any damage prior to commencing
installation.
The product is heavy! Make sure you have assistance when erecting
and installing the fi replace.
4.1 Floor
Foundations
Ensure that the fl oor is strong enough for the fi replace. See
«2.0 Technical data» for weights. It is recommended that fl ooring
which is not fastened to the foundations – so-called fl oating
fl ooring – is removed during installation.
Combustible fl oor protection
If the fi replace is to be mounted on a combustible fl oor, cover
the fl oor under and in front of the fi replace with a plate of metal
or other non- combustible material. The recommended minimum
thickness is 0,9 mm.
Jøtul recommends that any fl ooring made of combustible material, such
as linoleum, carpets, etc. should be removed from under the fl oor plate.
The plate must be in accordance with national laws and regulations.
Contact your local building authority regarding restrictions and
installation requirements.
4.2 Walls (fi g. 1a)
Distance to wall made of combustible material
You may use the fi replace with an uninsulated fl ue pipe provided
the distances to walls made of combustible materials are as
shown in fi g. 1.
Distance to wall with insulated fl ue pipe: Se fi g. 1.
Distance to walls covered by a firewall (fig. 1b
and fig. 1c)
Contact your local building authority regarding restrictions and
installation requirements.
Firewall requirement
The fi rewall must be at least 100 mm thick and be made of
brick, concrete-stone or light concrete. Other materials and
constructions with satisfactory documentation may also be used.
Distance to non combustible walls
By non combustible one means a non load-bearing wall of solid
brickwork/concrete.
Contact your local building authority regarding restrictions and
installation requirements.
8
4.3 Chimneys and fl ue pipes
•
The fi replace can be connected to a chimney and fl ue
pipe approved for solid fuel fi red appliances with fl ue gas
temperatures specifi ed in «2.0 Technical data».
•
The chimney's cross-section must be at least as big as
the fl ue pipe's cross-section. See «2.0 Technical data» when
calculating the correct chimney cross-section.
•
Several solid fuel fi red appliances can be connected to the
same chimney if the chimney's cross-section is suffi cient.
•
Connection to the chimney must be carried out in accordance
with the installation instructions from the supplier of the
chimney.
•
Before making a hole in the chimney the fi replace should be
test-mounted in order to correctly mark the position of the
fi replace and the hole in the chimney. See fi g. 1 for minimum
dimensions.
•
Ensure that the fl ue pipe is inclined all the way up to the
chimney.
•
Use a fl ue pipe bend with a sweeping hatch that allows it to
be swept.
Be aware of the fact that it is particularly important that
connections have a certain fl exibility in order to prevent
movement in the installation leading to cracks.
N.B. A correct and sealed connection is very important for the proper
functioning of the product.
Chimney draught; See «2.0 Technical data». If the draught is too strong
you can install and operate a fl ue damper to control the draught.
4.4 Assembly prior to installation
The product is delivered in a single packing case.
After unpacking the stove check that the stove is free of any
damage and that the regulating handles works.
4.5 Selfclosing doormechanism
The product is delivered with a selfclosing doormechanism. If
wanted this can be removed.
Fig. 3
g
g
A
1. Unscrew the screw and nut (fi g. 3 A).
2. Unhook and remove the spring.
B