DELAY START

WHAT IS IT? The delay start is the time in seconds (0-999sec) after the power on during
which the controller waits before being enabled to activate the electrical socket. During this
period of time the display shows the message "Delay" on the first row and the measure on the
second row (see figure on the left side). During the delay start the electrical socket can't be
activated but it is possible to enter the menu and modify the parameters and calibrations.

TIME ALARM

1) The socket activation stops (no tension to the electrical socket)
2) Green led On blinks
3) The display shows : "Tal" and the % activation on the first row and the measure on the second row.
NOTE: The time alarm has no effect on Manual mode operation
LEVEL CONTROL (upon request)
The closing of the level input contact, free of tension, while the controller is working, will
cause:
1) The electrical socket is disabled
2) the green ON led blinks
3) The display shows "Level" alternatively on the first row and the actual measure on the
When the level contact gets opened again, the controller returns to working mode compatible
with the actual inputs. NOTE: The level alarm suspends (but not reset) the counting of the
Alarm Time.
FLOW CONTROL (upon request)
The closing of the flow input contact, free of tension, will cause:
1) The electrical socket is disabled
2) the green ON led blinks
3) The display shows "Flow" alternatively on the first row and the actual measure on the
second row.
When the flow contact gets opened again, the controller returns to working mode compatible
with the actual inputs. NOTE: The flow alarm resets the counting of the Alarm Time.
DELAY START EDITING
Push and quickly release CAL button and scroll the menu using + and –
buttons till the display shows "Delay Start". Push CAL to enter the
submenu and then by pressing + and – button choice the value in seconds
(0-999). Push CAL to confirm and ESC to go back in measuring.
WHAT IS IT? The Time alarm is expressed in units (0-120unit) of activity. One unit is
equivalent to 1 minute of socket activation. The units counting starts from 0 when the
controller starts socket activation after the power on, increases during socket activation,
stops during level alarm and standby state, and is resettled when the power is off, when
the measure reaches the set point and during the flow alarm. When the counting reaches
the value memorized in Time alarm the controller goes in Time Alarm state:
Push and hold ESC button for 2 seconds to esc the Time Alarm state and to go back to
functioning. The time alarm counting restart from 0 when the controller powers the socket
again.
TIME ALARM EDITING
Push and quickly release CAL button and scroll the menu using + and –
buttons till the display shows "Alarm Time". Push CAL to enter the
submenu and then by pressing + and – button choice the value in units
(0-120).
Push CAL to confirm and ESC to go back in measuring.
second row.
Cod. 00.008.574 Rev 1.0