Power Supply and Wiring
Section 6
(continued)

Single Phase Connection

For small drives with diode rectifier front end it is possible to run a three phase output with a single phase
input. Only part of the three phase input bridge is used. Ripple current becomes 120 Hz rather than 360. This
places a greater demand on the DC filter components (capacitor bank and DC choke). The result is that the
drive must be derated to 50% current.
The chart below shows the full load output current ratings of the controller when single phase or 3 phase
power is used. If single phase input power is used the Motor Overload switches must be set to 50% or lower.
Supply
Frame
Voltage
208/230
460
Model
Size
Number
SPD20050
1
SPD20050F
SPD20075
SPD20075F
2
SPD20100
SPD20100F
SPD20150
SPD20150F
3
SPD20200
SPD20200F
SPD20250
SPD20250F
4
SPD20300
SPD20300F
SPD40050
SPD40050F
1
SPD40075
SPD40075F
SPD40100
SPD40100F
SPD40150
2
SPD40150F
SPD40200
SPD40200F
SPD40250
SPD40250F
3
SPD40300
SPD40300F
Nominal
HP Rating
3 Phase
1 Phase
Input
Input
5.0
2.0
7.5
3.0
10.0
5.0
15.0
7.5
20.0
10.0
25.0
12.0
30.0
15.0
5.0
7.5
10.0
15.0
20.0
25.0
30.0
12
Controller Full Load
Output Current Rating
3 Phase
1 Phase
Input
Input
17.8
8.1
26.4
10.9
37.0
17.8
47.4
26.4
60.6
33.0
76.0
40.2
94.0
47.4
8.9
13.2
18.5
23.7
30.3
37.5
47.0