Setting the price
Price setting for unit of given quantity (electricity, cold water, hot water, gas)
Price - is the default value to be calculated if no time interval is set.
• + – add a new type of energy price, this price is valid for a specifi c period,
beyond the set period is calculated with the default price.
Setting for each phase
Voltage monitoring (overvoltage, under-voltage) - sets the upper level in the
range of 138-276V (overvoltage) and the lower level in the range of 35-99%
of the upper level. If the phase moves from this set band, the output relay
switches on / off the contact (if this function is indicated).
• Phase L1, L2, L3 – Setting for Phase 1, Phase 2, and Phase 3
• Threshold – setting the limit value of the quantities
• Hysteresis – fi xed deviation attributed to the limit value when returning
to the supervised zone
• WARN – Activating this button activates the Warning function
• RELAY – by activating this button it is possible to switch the relay when
the defi ned value is exceeded
• Over Voltage (V) – overvoltage
• Under Voltage (V) – Under-voltage
• Phase Loss (V) – monitors loss of voltage on individual phases
• THD Voltage (%), THD Current (%) – percentage deviation expressing
distortion from ideal harmonic fl ow.
• Asymmetry (%) – the asymmetry rate between the phases is set at 5-20%.
If the set asymmetry is exceeded, the relay can be switched on / off .
Main setup
• Web interface
• Currency setup
• Tarrif setup
• Timezone setup
• Device Name