Technical Parameters - Elko EP iNELS RFPM-2M Manual De Usario

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 36
RFPM-2M
Energy gateway
EN

Technical parameters

Supply / measured voltage:
Supply voltage tolerance:
Closed relay power input:
Switching voltage level:
Output RELE
Number of contacts:
Max. current:
Switching power:
Mechanical service life:
Electrical service life:
Relay reaction:
Interface RF Control
Communication protocol:
Broadcasting frequency
Signal transfer method:
Output for antenna:
Antenna RF:
Range in open space:
Controlling
Controlling:
Button Reset:
Interface Wi-Fi
Wi-Fi mode:
Standard:
Wi-Fi Security:
Frequency range Wi-Fi:
Antenna Wi-Fi:
Range:
Interface Ethernet
Network settings:
Transfer speed:
Connector:
Default IP address / IP address of
bootloader:
Measuring
Pulse inputs:
Tariff inputs:
Option of switching inputs:
Separation by isolation of power and
control circuits:
Probes measuring current:
Wireless consumption sensor:
Measuring circuit
Network:
Frequency:
Accuracy:
Current measuring coil:
Wire diameter:
Other data
Working temperature:
Storage temperature:
Operating position:
Mounting:
Protection:
Overvoltage category:
Degree of pollution:
Cross-section of connecting wires (mm
2
):
Dimension:
Weight:
* Max Tightening Torque for antenna connector is 0.56 Nm.
Attention:
When you instal iNELS RF Control system, you have to keep minimal distance 1 cm between each units.
Between the individual commands must be an interval of at least 1s.
Made in Czech Republic
230 V AC / 50-60 Hz, 1f / 3f +N
+15/-20%
5 VA
140 V, +10/-20%
1 NO/NC switches L1
16 A / AC1
4000 VA (AC1)
3 x 10
7
0.7 x 10
5
two-way addressed message, see manuals
RF Touch Compatible
866 MHz, 868 MHz, 916 MHz
two-way addressed message
SMA - FEMALE*
1 dB (part of suply)
up to 100 m
WEB / Mobile Applications
Bootloader (stisk >2 s) / Unit reset (press >10 s)
AP Bridge / AP LAN / Client
IEEE 802.11 b/g/n / 2.4 GHz
WEP, WPA-PSK, WPA2-PSK
RP - SMA - FEMALE*
1 dB (part of suply)
up to 20 m
static IP / DHCP Client
10 / 100 Mbit / s
RJ45
192.168.1.2
PULS1 (S0), PULS2 (S0)
TARF1, TARF2 - binary combination
switching by contact/opening by collector
reinforced Insulation
(Cat. II surges by EN 60664-1)
3 x CT-50
RFTM-1
1f-3f
50 - 60 Hz /±10 %
Class 1.0
max. 50 A (current transformer CT50)
max. 16 mm
-20 .. + 35°C
-30 .. +70°C
vertical
DIN rail EN60715
IP20 from front panel / IP40 in cover
II.
2
max. 1x 2.5, max. 2x 1.5 / with a hollow max. 1.5
90 x 52 x 65 mm
125 g
ELKO EP, s.r.o. | Palackého 493 | 769 01 Holešov, Všetuly | Czech republic | e-mail: elko@elkoep.com
Notifi cation and saving changes
Save any changes you have made by pressing APPLY or APPLY & RESTART. If the change needs to be
restarted, it will request it.
Notifi cation of successful download
Notifi cation of incorrect data download
Data download notifi cation
Notifi cation of successful update of FW
and restart of web page after 15 sec
Recalculation of new data (browser freezes
when new data is downloaded)
Warning
Instruction manual is designated for mounting and also for user of the device. It is always a part of its
packing. Installation and connection can be carried out only by a person with adequate professional
qualifi cation upon understanding this instruction manual and functions of the device, and while
observing all valid regulations. Trouble-free function of the device also depends on transportation,
storing and handling. In case you notice any sign of damage, deformation, malfunction or missing
part, do not install this device and return it to its seller. It is necessary to treat this product and its
parts as electronic waste after its lifetime is terminated. Before starting installation, make sure that all
wires, connected parts or terminals are de-energized. While mounting and servicing observe safety
regulations, norms, directives and professional, and export regulations for working with electrical
devices. Do not touch parts of the device that are energized – life threat. Due to transmissivity of RF
signal, observe correct location of RF components in a building where the installation is taking place.
RF Control is designated only for mounting in interiors. Devices are not designated for installation
into exteriors and humid spaces. The must not be installed into metal switchboards and into plastic
switchboards with metal door – transmissivity of RF signal is then impossible. RF Control is not
recommended for pulleys etc. – radiofrequency signal can be shielded by an obstruction, interfered,
battery of the transceiver can get fl at etc. and thus disable remote control.
Support: +420 778 427 366
EN
www.elkoep.com
02-5/2018 Rev.1
Notifi cation of successful data storage
Notifi cation of failed data storage
Notifi cation of forced restart after data saving
Notifi cation of restart of RFPM and
refresh of web page after 15 sec
7/7

Publicidad

Tabla de contenido
loading

Tabla de contenido