Parameter Table - YASKAWA V1000 Serie Guía De Referencia Rápida

Ocultar thumbs Ver también para V1000 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

6

Parameter Table

This parameter table shows the most important parameters. Default
settings are bold type. Refer to the Technical Manual for a complete list
of parameters.
Par.
Name
Initialization Parameters
Selects which parameters are accessible via the
digital operator.
Access Level
A1-01
0: Operation only
Selection
1: User Parameters
2: Advanced Access Level
Selects the Control Method of the drive.
0: V/f Control
Control Method
A1-02
2: Open Loop Vector (OLV)
Selection
5: PM Open Loop Vector (PM)
Note: Not initialized with A1-03!
Resets all parameters to default. (returns to 0
after initialization)
0: No Initialize
Initialize
1110: User Initialize (The user must first set user
A1-03
Parameters
parameter values and then store them using
parameter o2-03)
2220: 2-Wire Initialization
3330: 3-Wire Initialization
Operation Mode Selection
0: Operator - d1-
Frequency
1: Analog input A1 or A2
b1-01
Reference
2: Serial communication - RS-422/485
Selection
3: Option board
4: Pulse input (Terminal RP)
0: Operator - RUN and STOP keys
Run Command
1: Terminals - Digital inputs
b1-02
Selection
2: Serial Com - RS-422/485
3: Option board connected
Selects the stopping method when the run
command is removed.
0: Ramp to Stop
Stopping Method
b1-03
1: Coast to Stop
Selection
2: DC Injection Braking to Stop
3: Coast with Timer (a new run command is
ignored if received before the timer expires)
Reverse
0: Reverse enabled
b1-04
Operation
1: Reverse prohibited
Selection
Switches the output phase order.
Phase Order
b1-14
0: Standard
Selection
1: Switch phase order
DC Injection Braking
Sets the frequency at which DC Injection
DC Injection
Braking starts when Ramp to Stop (b1-03 = 0) is
b2-01
Braking Start
selected. If b2-01< E1-09, DC Injection Braking
Frequency
starts at E1-09.
Sets the DC Injection Braking current as a
DC Injection
percentage of the drive rated current.
b2-02
Braking Current
In OLV the DC excitation current is determined
by E2-03.
DC Inj.
Sets the time of DC Injection Braking at start in
Braking Time/
b2-03
units of 0.01 seconds. Disabled when set to 0.00
DC Excitation
seconds.
Time at Start
DC Inj.
Sets the DC Injection Braking time at stop.
b2-04
Braking Time at
Disabled when set to 0.00 seconds.
Stop
Acceleration/ Deceleration
Sets the acceleration time 1 from 0 to the max.
C1-01
Accel Time 1
output frequency.
Sets the deceleration time 1 from the max. output
C1-02
Decel Time 1
frequency to 0.
C1-03 to
Accel/Decel
Set the accel/decel times 2 to 4 (set like C1-01/
C1-08
Times 2 to 4
02).
C2-01
S-Curve 1
S-curve at acceleration start.
YASKAWA Europe TOMP_C710606_75A V1000 IP66 - Quick Start Guide
Description
values
Par.
Name
C2-02
S-Curve 2
S-curve at acceleration end.
C2-03
S-Curve 3
S-curve at deceleration start.
C2-04
S-Curve 4
S-curve at deceleration end.
Slip Compensation
Increase if the speed is lower than the frequency
Slip
reference.
C3-01
Compensation
Decrease if the speed is higher than the
Gain
frequency reference.
Slip
Decrease the setting when the slip compensation
C3-02
Compensation
is too slow.
Delay Time
Increase the setting when the speed is not stable.
Torque Compensation
Increase this setting when the torque response is
Torque
slow.
C4-01
Compensation
Decrease this setting when speed/torque
Gain
oscillations occur.
Increase this setting when speed /torque
Torque
oscillations occur.
C4-02
Compensation
Decrease the setting when the torque response is
Delay Time
too slow.
Duty Mode and Carrier Frequency
0: Heavy Duty (HD) - Constant torque
Normal/ Heavy
applications
C6-01
Duty Selection
1: Normal Duty (ND) - Variable torque
application
1: 2.0 kHz
2: 5.0 kHz
3: 8.0 kHz
Carrier
4: 10.0 kHz
C6-02
Frequency
5: 12.5 kHz
Selection
6: 15.0 kHz
7 to A: Swing PWM1 to 4
F: User defined
Frequency References
d1-01 to
Frequency
Set the multi-speed references 1 to 16.
d1-16
Reference 1 to 16
d1-17
Jog Speed
Jog speed
V/f Pattern
Input Voltage
E1-01
Input Voltage
Setting
Max. Output
For a linear V/f characteristics, set the same
E1-04
Freq.
values for E1-07 and E1-09. In this case, the
setting for E1-08 will be disregarded.
Max. Output
E1-05
Ensure that the four frequencies are set
Voltage
according to these rules or OPE10 fault will
occur:
E1-06
Base Frequency
E1-04 E1-06
Middle Output
E1-07
Freq.
Mid. Output
E1-08
Voltage
Min. Output
E1-09
Freq.
Min. Output
E1-10
Voltage
E1-13
Base Voltage
Motor Data
Motor Rated
E2-01
Automatically set during Auto-Tuning.
Current
Motor rated slip in hertz (Hz).
E2-02
Motor Rated Slip
Automatically set by Rotational Auto-Tuning.
Motor No-Load
Magnetizing current in Ampere.
E2-03
Current
Automatically set by Rotational Auto-Tuning.
Number of motor poles.
E2-04
Motor Poles
Automatically set by Auto-Tuning.
6 Parameter Table
Description
E1-07 E1-09
Output voltage
(E1-05)
(E1-13)
(E1-08)
(E1-10)
(E1-09)
(E1-07)
(E1-06)
(E1-04)
Output frequency
EN 21

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido