Example 2: Well, 7.50m maximum water level from ground of the well, Display m
(fill level 4.20m) relay switching function is desired.
SmartBox
Relay 1 has to protect the pump against running dry (switch off)
Relay 1- on at 99%-10% - off at < 10%
Step
1.Measure probe
2.Liquid
3.Tank shape
4.Tank volume
5.Tank height
5b.Filling limit
6.View View details
7.Relay 1
7.Relay 2
8.Exit press [+] key to go to
12.Unit
13.Rounding
14.Exit
press [Enter] to see the indication
Example 3: Buried tank, cylindrical, horizontal, for 100600 litres diesel oil
Inner height 288.6cm, (fill level 54cm)
SmartBox
Limit value message on the device at minimum level <25%
Acoustic alarm - on at <25% - off at >27%
Step
1.Measure probe
2.Liquid
3.Tank shape
4.Tank volume
5.Tank height
5b.Filling limi
6.View View details
6.Beepe
r
7.Relay
8.Exit
press [Enter] to see the indication
part no. 28 100 57 f
2 Probe 0 - 1000mbar, indication in m water column
®
®
3 Standard probe 0 - 250mbar
t
®
SmartBox
1 / SmartBox
Entries / selection
1000mbar (set with [+] / [-] keys)
Water
(set with [+] / [-] keys)
Linear
7500L
(set with [+] / [-] keys)
750cm
(set with [+] / [-] keys)
99%=743cm (set with [+] / [-] keys)
Fillspace+Percnt
display 2. line - (set with [+] / [-] keys)
Active Switch-on: 99%
Switch-off: 10%
(set with [+] / [-] keys)
Deactive
m
(set with [+] / [-] keys)
Automatically
Water
-3.23m
Entries / selection
250mbar
Diesel
Cyl. > 50.000L
100.600L (exact value from volume table
set with [+] / [-] keys)
288.6cm
(exact value from volume table
set with [+] / [-] keys)
99%=743cm (set with [+] / [-] keys)
Percent+Level
display 2. line - (set with [+] / [-] keys)
Active
Switch-on:
Switch-off 27%
Deactive
Diesel
12.800L
13%
®
2 / SmartBox
4.20m
56%
(set with [+] / [-] keys)
(set with [+] / [-] keys)
(set with [+] / [-] keys)
25%
(set with [+] / [-] keys)
54cm
®
3
13 / 20