Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Non-combustible wall (all the way through)
The fi replace can be installed with a minimum of 100 mm to
non-combustible wall if the distance from the fi replace to all
combustible materials are a minimum of 300 mm.
Non-combustible materials mean materials like brick, clinker,
concrete, mineral wool, cilicate plates etc (materials that do
not burn). Note! A short distance to non-combustible wall
may lead to desiccation and discoloration of paint and cause
cracking.
3.4 Ceiling
There must be a minimum distance of 700 mm to a combustible
ceiling above the fi replace.
Fresh air supply
The air used for combustion in any well-insulated house needs
to be replaced. This is particularly important in houses with
mechanical ventilation. Such replacement air can be procured
in several ways. The most important thing is to supply the air
to the room where the stove is placed. Place the outside wall
valve as close to the stove as possible and make sure that it
can be closed when the stove is not in use.
For the fresh air supply connection, follow the national and
local building regulations.
Important! Ensure that air vents in the room where the
fi replace is located are not blocked.
Closed combustion system
Use the stove's closed combustion system if you live in recently
built, airtight dwellings. Connect the external combustion air
through a ventilation pipe through the wall or the fl oor.

Air supply

The amount of combustion air for Jøtul's products is approximately
20-40 m 3 /h. The outside air connection may be fi tted directly to
the Jøtul F 602 ECO through:
the bottom
through a fl exible supply hose from the outside/chimney
(only if the chimney has its own duct for external air) and to
the product's outside air connector.
Through an outside wall
Through the fl oor and ground plate
Through the fl oor and basement
ENGLISH
7

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido