500 VDC
MEGGER
Figure 19
A record should be kept of the readings taken from the time the cable is first installed on the pipe. A history of the insulation resistance
reading can be helpful in spotting moisture ingress into the electrical system (by seeing a gradual decline in the insulation resistance or
physical damage to the heating cable (sharp decline in the insulation resistance). A sample record for this is shown in Figure 20. (See
following page)
®
© BriskHeat
Self Regulating Heating Cable
FOR HEATING CABLES WITH BRAID AND OUTER
JACKET
Test A - (solid lines) from heating cable bus wires to braid.
Test B - (dotted lines) from braid to metal pipe.
Corporation. All rights reserved.
25
BRISKHEAT PERIOD INSPECTION RECORD
Freeze Protection Circuits -
Perform these checks as season requiring use approaches.
Temperature Maintenance Circuits -
Perform these checks at least twice per year.
Maintenance Checks for _______________________________ Month _______________________ Year_________________
Visual inspection inside connection box
corrosion, moisture, etc.
Damage or cracks (leaks) in insulation
seals at valves, hangers, pumps, etc.
Heating cable properly connected and
grounded. heating cable and connections
insulated from connection box.
Thermostat checked for moisture, corrosion,
set point, switch operation, and capillary
damage
Megger tests performed at power
connection with both bus wires disconnected
from power wiring.
Circuit voltage at power connection.
Circuit amperage after 5 minutes
Pipe temperature at time amps were measured.
Watts/Ft.
Volts x Amps = w/ft.
feet
All connections, boxes, and thermostats
have been resealed.
End seals, covered splices and tees marked
On insulation cladding.
Remarks & Comments
Periodic Inspection Record Form
The Periodic Inspection record Form may be used in one of two ways:
1.
One sheet per circuit - The results of periodic tests of a single circuit are posted in vertical columns, beginning on the left and
working toward the right. This allows easy comparison of test values for up to seven test sequences on an individual circuit.
2.
One circuit per column - Test data for a single test sequence on as many as seven circuits can be recorded on a single sheet.
®
© BriskHeat
Self Regulating Heating Cable
Circuit Number
Heater Type
Circuit Length
Initial
Date
Initial
Date
Initial
Date
Set Point
Initial
Date
Reading
Initial
Date
Reading
Reading
Reading
Initial
Date
Initial
Date
Initial
Date
Figure 20
Corporation. All rights reserved.
26