Anomalies: these are "minor" problems, which do not bring the UPS to a halt, but can reduce its performance or inhibit
the use of some of its functions.
CODE
A03
A04
A05
A06
A07
A08
A09
A10
A11
A13
A14
A15
A16
A18
A19
A20
A21
A22
A23
A24
A25
A26
A27
A29
A30
A31
A32
A33
A34
A35
A36
A37
A38
A39
A40
IV331 Rev.000 SIEL S.p.A.
Data di emissione: 2011-08-22
DESCRIPTION
Inverter not synchronised
External synchronism failed
Overvoltage on input line of Phase1
Overvoltage on input line of Phase2
Overvoltage on input line of Phase3
Undervoltage on input line of Phase1
Undervoltage on input line of Phase2
Undervoltage on input line of Phase3
Input frequency outside tolerance limits
Voltage on bypass line of Phase1 out of tolerance limits
Voltage on bypass line of Phase2 out of tolerance limits
Voltage on bypass line of Phase3 out of tolerance limits
Bypass frequency out of tolerance limits
Voltage on bypass line out of tolerance limits
High current peak on phase 1 output
High current peak on phase 2 output
High current peak on phase 3 output
Load on Phase1 > user-defined threshold
Load on Phase2 > user-defined threshold
Load on Phase3 > user-defined threshold
Output isolator open
Positive branch batteries missing or battery fuses open
Negative branch batteries missing or battery fuses open
System temperature probe damaged
System temperature < 0°C
System temperature too high
Temperature of heat sink 1 < 0°C
Temperature of heat sink 2 < 0°C
Temperature of heat sink 3 < 0°C
Internal battery temperature probe damaged
Internal battery overtemperature
External battery temperature probe damaged
External battery overtemperature
Positive branch batteries must be replaced
Negative branch batteries must be replaced