5
5.1
DIRECTION OF PHASE ROTATION
On a three-phase electrical network:
1.
connect the 3 leads to the instrument, matching the
markings.
2.
connect the 3 alligator clips to the 3 phases of the network
to be tested.
3.
the lighting of the display indicates that the instrument is in
operation.
When the 3 phase indicators (L1, L2, L3) are lit, the
clockwise (or anticlockwise) rotation arrow indicates the
direction of phase rotation.
Warning: the wrong direction of rotation may be displayed if a lead
is connected by mistake to the neutral of the network.
USING THE INSTRUMENT
17