Calibrating the temperature display
1. Switch off the DIGIMON
2. Plug in the thermocouples (K-type).
Room and measurement temperatures must remain constant at 25 +/-3°C
and be stable for at least 20 minutes. The thermocouple cables must be
straight (unwound).
During calibration, you should neither touch the cables nor the plugs.
3. Hold down the
button.
The display shows "Password" 000
4. Press the
5. Press the
Display shows "T-call"
6. Press the
7. During calibration, ensure that both thermocouples are connected to the
DIGIMON.
The display shows
LP
00xxx
27.0°C
The current temperature displayed on the DIGIMON should not deviate
by more than +/-0.5°C from the room temperature.
8. Press the
The display shows:
LP
End
00xxx
27.0°C
18
LIGHT
button and switch on the device using the
+
-
R
R
/
button to select code 018.
SET
button to exit.
-
R
button and then the
SET
button to confirm.
Instruction Manual DIGIMON-SE / DIGIMON4
SET
button to calibrate.
(low pressure side)
Temperature code
Current temperature