Setup / Settings - Delta SOLIVIA 2.5 EU G3 Manual De Operación Y Instalacion

Ocultar thumbs Ver también para SOLIVIA 2.5 EU G3:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 155
In order to set up the device, follow these procedures carefully:
1. Turn off the DC disconnector.
2. DC connection: First, connect the PV module strings to the DC Tyco Solarlok connectors (ensure
correct polarity).
3. AC connection: Please install the Wieland AC mating connector to the AC output cable and then
plug the AC connector to the solar inverter. Please make sure, that the sleeve nut is properly
fi xed and tighten.
4. Before switching on the power, check all feeders and connections one last time.
5. Turn on the DC disconnector.
6. Close the circuit breaker on the AC output side.
7. In case of suffi cient PV voltage (UPV > 150 V), the device now goes into the feed-in operation.
8. In case of a new installation the time and date have to be set in sub-menu S (Setup) (see § 7.3.8).
All unoccupied connectors and interfaces must be sealed using the provided sealing
plugs.
6.10

Setup / settings

The default display language for solar inverters leaving the Delta factory is set to English.
After connecting to correct DC voltage and running through self-test, you will be asked to specify the
network ID and to select the desired country (see § 7.3.8.2) (countries available: Belgium, Czech
Republic, France, Germany, Greece, Italy, Portugal, Spain and United Kingdom).
The selection has to be confi rmed another time by the user. Once confi rmed, the network ID and the
country selection are stored to the controller memory – and the solar inverter is ready for operation.
Please note that the enter keys on the display are locked, if there is no input entry within 5
minutes. To unlock the enter keys, you need to switch off the DC voltage and then switch it on again.
Country selection
Enter network ID
Up *
Increase network ID
* Timeout if no key is pressed (within 5 minutes)
16
Down *
ENTER *
Decrease network ID
Up *
Next country
ESC *
Select country
Down *
Country before
Operation and installation manual SOLIVIA 2.5 EU G3
Possible countries:
Belgium
Czech Republic
France
French island (60 Hz)
Germany
Greece continent
Greece island
Italy (50 Hz / 49 Hz)
Italy (51 Hz / 49 Hz)
Portugal
Spain (51 Hz / 49 Hz)
Spain (51 Hz / 48 Hz)
United Kingdom
ENTER *
Normal mode

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Solivia 3.3 eu g3

Tabla de contenido