Installation
Step 3: Test eyewash unit
1. After completing installation, test the unit by pulling the front flap down
and all the way out. This action should activate the water spray. Check
the sprayheads for proper water flow and look for possible water leakage
throughout the unit. Visually inspect all areas of the heater jacket to verify
proper operation of the heating element.
Visually inspect the eyewash unit weekly for cleanliness and proper
solution level (per ANSI Standard Z358.1-2009). When the water level
drops below the 15-minute fill line, the tank must be emptied and then
refilled. To refill the eyewash tank, follow the procedures outlined in Step 2
on page 4.
2. Attach the eyewash inspection tag (supplied) to the eyewash unit. This
tag is to be used for weekly inspection documentation. Hook-and-loop
fasteners are provided to attach the tag to the unit.
3. If the eyewash unit is not working properly, remove it from the hazard
area and contact Bradley Corporation immediately.
Tank
Pedestal
Cap
Optional Heater Jacket Junction Box
LED Light
Green Light: an indication that the unit has power.
•
•
Amber Light: an indication that the heater is in operation and heating the unit. The light will be on only while the heater is operating
(heating the unit).
Red Light: an indication that the thermostat needs to be reset. To reset the thermostat, follow the procedure outlined below.
•
1. Remove the top of the heater jacket.
2. Find the "reset" button on the thermostat (located on the tank) and press the button.
•
After pressing the button, check to be sure that the red light is off and that the green light is on (the amber light will be on only
if the heater is operating). If the red light is still on, press the "reset" button again.
3. Replace the top of the heater jacket.
Bradley • 215-1714 Rev. D; ECN 12-05-016E
Snorkel
Clamp
Latch
Pierce
Drain Hole
Position the heater pad evenly
around the drain hole. Do not
block the drain hole.
Top View of Pedestal
8/9/2012
S19-921H, S19-921HR