Electrical Connection; Plug Type A - Biral LX Instrucciones De Instalación Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 59
45

Plug Type A

Connecting diagram
3 × 400 V~
* Coil Thermal Protectors (WSK)
BC 712 W, BC 752.
WSK terminals are not provided
on short-circuit proof motors (BC 753).
english

5. Electrical connection

The electrical connection must be made by an expert.
I.E.E. regulations must be complied with.
Please observe NIN (CENELEC) regulations.
In the case of higher water temperatures (over 80 °C), use an
appropriate heat-resistant connecting line.
The connecting line must not touch the piping, or the pump
and motor casings. In the case of twin pumps (series LXD ...),
a separate connecting line with all-pole switch is to be provided
for each pump motor (operating reliability!).
Be sure to provide protection against dripping water and a mains
lead cleat at the cable inlet to the connection box (gland)!
(rated current × 1.5) mx. 16 A, delay-action
Preliminary fuse:
Wire cross section: max. 2.5 mm
Starting current:
max. 3 x rated current.
The electrical connection must be made in accordance with the
data plate. To simplify later replacement, the electrical connection
should be looped.
5.1 Plug Type A (3 × 400 V~)
Warning:
With mains connection 3 × 400 V~
only use plug Type A!
If plug Type B is used
(as accessory for 1 × 230 V~/3 × 230 V~)
the motor will be destroyed!
The motor has two speed steps.
With the Type A plug, 2 speeds can be set manually
(see Section 5.2 «Power setting» ).
If the voltage is wrong, the motor will be damaged.
Warning:
Motor protection (CEC, 11,12) must be connected.
(Accessory control unit BC 712 W, BC 752, etc.)
Note:
- With power supply 1× 230 V~/3 × 230 V~
plug Type B must be requested.
- For external speed switchover, step I, II.
2
.

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

LxdHxHxd

Tabla de contenido