3.3 A Basic Configuration Installation
The basic configuration of the panel can be made entirely from the keypad of the panel
itself, but we recommend using the configuration software provided so that the process
will be simpler and faster.
Here are the steps for a basic installation.
SelecttheLanguage.See section
DateandTimeSettings. To set the date and time on the panel see section
Name the installation. To enter the name of the installation, and the maintenance
company & phone
Setaloop. Use loop autosearch so the system will scan and show all the items it finds.
This search should match the items found with the plans for the installation. To access
the AUTOSEARCH LOOP menu.
Configurezones. The installation can be divided into zones, this allows the installation
to be structured according to installation requirements.
Configurethepoints.A point can be assigned a name that identifies its location and
zone. The points can be disabled if necessary.
Setactions. An action is the "cause and effect" rule which applies when a fire event
occurs. To set up a move, you first define an input generated by the event and then define
the output that is required. The outputs may be associated with a time delay in seconds,
to avoid false alarms in case of immediate actions.
Once all the steps outlined above have been carried out, the system is configured to
protect the installation.