UK
Interface functions
1 s: - Switch ECO ON/OFF
5 s: - Enable/disable both alarms
40 s: - Reset
Relay Indication
- On: Relay closed -> System set in forced
ECO mode
- Off: Relay open -> System set in normal
mode
SIM card considerations
Use a mobile phone to:
• Deactivate SIM card PIN code using the security option on your
mobile phone.
• Test the SIM card is working properly when trouble shooting a system.
Note that some types of SIM cards become inactivated if they have
not been used for some time. This can be prevented by the heartbeat
function that will send a SMS from the remote access module R-56
with a configurable interval.
See picture B: Uponor Smatrix Remote Access Module R-56 SMS package
2
U P O N O R S M AT R I X R E M O T E A C C E S S M O D U L E R - 5 6 S M S
Bicolor LED indicates alarm status
green: alarm 1 and 2 available
red: contact opened
GSM Network Indication
Constantly On: No GSM Signal
Slow Blink: GSM Signal OK
Fast Blink: Receiving SMS