SMS Setup sequence
Use the forward function in your phone.
• Start with the above message and modify the PHONE parameter to
your mobile phone number. Send and then check once again with
PASS CONF that the setting was accepted. Do not send more than
1 single SMS message
• Start with the new configuration answer and modify the alarm temp
to preferred value. This will be dependent to the setback value in the
Uponor Smatrix Base/Wave/Wave PLUS controller.
For example:
6 °C setback on the controller when in ECO mode.
21 °C normal set point in the room where the remote access module
R-56 is mounted.
2 °C safety margin.
ALARMTEMP = 21 – 6 – 2 = 13. ie. the remote access module R-56
will send an alarm when the temperature drops below 13 °C.
• Repeat the sequence with PASS CONF and then send new setting:
OUTPUT=0
• Repeat once again and then send a new PASS variable. Take care
to save the password. Otherwise you will not be able to access the
remote access module R-56 remotely.