Battery Replacement

Under normal conditions, the original battery in your UPS will last several years. Battery replacement should only be performed by qualified
personnel. Refer to "Battery Warnings" in the Safety section for complete battery safety information.
The VS450T requires one 12V DC, 4.5Ah replacement battery.
The VS650T requires one 12V DC, 7Ah replacement battery.
The VS950T requires one 12V DC, 7Ah replacement battery.
For further information about replacement compatibility and ordering, visit Tripp Lite on the Web at www.tripplite.com/products/battery-finder.
Battery replacement must be done using the same battery type and quantity: 12V DC sealed lead acid, 6 cell, and in
compliance with UL 1989.
CAUTION: Risk of energy hazard. Before replacing batteries, remove conductive jewelry such as chains, wrist watches
and rings. High energy passing through conductive materials may cause severe burns.

Storage and Service

Storage
To avoid battery drain, all connected equipment should be turned off and disconnected from the UPS. Press and hold the power button
one second and disconnect the unit from AC power. Your UPS will be completely turned off (deactivated), and will be ready for storage. If you
plan on storing your UPS for an extended period, fully recharge the UPS batteries every three months. Plug the UPS into a live AC outlet, turn
it on by pressing and holding the power button
batteries discharged for a long period of time, they will suffer a permanent loss of capacity.
Service
A variety of Extended Warranty and On-Site Service Programs are available from Tripp Lite. For more information on service, visit
www.tripplite.com/support. Before returning your product for service, follow these steps:
1. Review the installation and operation procedures in this manual to insure that the service problem does not originate from a misreading of
the instructions.
2. If the problem continues, do not contact or return the product to the dealer. Instead, visit www.tripplite.com/support.
3. If the problem requires service, visit www.tripplite.com/support and click the Product Returns link. From here, you can request a Returned
Material Authorization (RMA) number, which is required for service. This simple online form will ask for your unit's model and serial
numbers, along with other general purchaser information. The RMA number and shipping instructions will be emailed to you. Any damages
(direct, indirect, special or consequential) to the product incurred during shipment to Tripp Lite or an authorized Tripp Lite service center
is not covered under warranty. Products shipped to Tripp Lite or an authorized Tripp Lite service center must have transportation charges
prepaid. Mark the RMA number on the outside of the package. If the product is within its warranty period, enclose a copy of your sales
receipt. Return the product for service using an insured carrier to the address given to you when you request the RMA.