Param.
Function
P0511 Decimal Point SoftPLC
Eng. Unit 1
P0512 SoftPLC Eng. Unit 2
P0513 Decimal Point SoftPLC
Eng. Unit 2
P0520 PID Proportional Gain
P0521 PID Integral Gain
P0522 PID Differential Gain
P0525 PID Setpoint by HMI
P0526 PID Setpoint Filter
P0527 PID Action Type
P0528 Process Variable Scale
Factor
P0529 Process Variable
Indication Form
P0533 X Process Variable
Value
P0535 Wake Up Band
P0536 P0525 Automatic
Setting
P0680 Logical Status
P0681 Speed at 13 bits
P0682 Serial/USB Control
P0683 Serial/USB Speed Ref.
P0684 CO/DN Control
P0685 CO/DN Speed Ref.
Quick Parameter Reference, Faults and Alarms
Adjustable
Range
0 = wxyz
1 = wxy.z
2 = wx.yz
3 = w.xyz
See options in P0510
See options in P0511
0.000 to 9.999
0.000 to 9.999
0.000 to 9.999
0.0 to 100.0 %
0 to 9999 ms
0 = Direct
1 = Reverse
10 to 30000
0 = wxyz
1 = wxy.z
2 = wx.yz
3 = w.xyz
0.0 to 100.0 %
0.0 to 100.0 %
0 = Inactive
1 = Active
0000h to FFFFh
Bit 0 to 3 = Reserved
Bit 4 = Quick Stop
Bit 5 = 2
Ramp
nd
Bit 6 = Config. status
Bit 7 = Alarm
Bit 8 = Running
Bit 9 = Enabled
Bit 10 = Clockwise
Bit 11 = JOG
Bit 12 = Remote
Bit 13 = Undervoltage
Bit 14 = Automatic(PID)
Bit 15 = Fault
-32768 to 32767
0000h to FFFFh
Bit 0 = Ramp Enable
Bit 1 = General Enable
Bit 2 = Run Clockwise
Bit 3 = JOG Enable
Bit 4 = Remote
Bit 5 = 2
Ramp
nd
Bit 6 = Quick Stop
Bit 7 = Fault Reset
Bit 8 to 15 = Reserved
-32768 to 32767
See options in P0682
-32768 to 32767
Factory
User
Propr.
Setting
Setting
1
3
0
1.000
0.430
0.000
0.0 %
50 ms
0
1000
1
90.0 %
0.0 %
0
cfg
ro
ro
ro
ro
ro
ro
Groups Page
HMI,
5-8
SPLC
HMI,
5-9
SPLC
HMI,
5-9
SPLC
13-8
13-8
13-8
13-8
13-9
13-9
HMI
13-9
HMI
13-10
I/O
13-10
I/O
13-10
13-11
READ,
7-13
NET
READ,
17-5
NET
READ,
7-14
NET
READ,
17-3
NET
NET
17-3
READ,
17-3
NET
CFW500 | 17