GENERAL TECHNICAL DATA
Size
Total cooling capacity (1)
Sensible cooling capacity (1)
Heat output (2)
Heating capacity supplementary coil (3)
Pressure drop standard coil (1)
Pressure drop auxiliary coil (3)
Max absorbed power
Absorbed current at nominal conditions
Current absorbed at maximum conditions
Number - diameter impellers
Rated air flow
Useful head (basic unit with filter)
Standard coil hydraulic connections
Auxiliary coil hydraulic connections
Weight
Dimension (A)
Dimension (B)
Dimension (C)
Sound pressure level minimum speed (4)
Sound pressure level speed average (4)
Sound pressure level speed maximum (4)
Electrical power supply
(1)
Room temperature 27°C-50% R.H.; water in/out temperature 7/12°C
(2)
Room temperature 20°C - 50% R.H.; water in/out temperature 45/40°C
12
English 07/13
602
703
kW
5,2
6,6
kW
3,5
4,5
kW
5,0
6,3
kW
9,1
9,1
kPa
16
18
kPa
9
9
kW
0,37
0,37
A
1,30
1,30
A
1,70
1,70
N°-mm
2-160
2-160
m
3
/h
1300
1300
Pa
67
65
Gas
1/2"
1/2"
Gas
1/2"
1/2"
kg
41
43
mm
900
900
mm
690
690
mm
295
295
dB(A)
47
47
dB(A)
50
50
dB(A)
53
53
V-Ph-Hz
(3)
Room temperature 20°C - 50% RH; water in/out temperature 70/60°C
(4)
Measurement to 1 m by the point of air outlet
I
803
904
1003
8,5
10,2
12,1
5,8
6,9
8,2
7,4
9,3
11,3
11,8
11,8
16,7
19
15
26
14
14
13
0,44
0,44
0,90
1,55
1,55
2,30
1,70
1,70
3,30
2-160
2-160
2-200
1600
1600
2200
72
66
115
3/4"
3/4"
1"
1/2"
1/2"
1/2"
50
52
63
1050
1050
1250
690
690
750
295
295
315
48
49
53
52
53
55
56
57
59
230~50
A
1104
15,8
10,7
14,5
18,0
24
15
0,90
2,60
3,30
2-200
2500
89
1"
1/2"
65
1250
750
315
54
58
61
HWD