High Static Pressure Ducted Type (E1 Type) - Panasonic S-22MU1E5 Instrucciones De Instalación

Acondicionador de aire con sistema vrf - para refrigerante r410a
Ocultar thumbs Ver también para S-22MU1E5:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 171

■ High Static Pressure Ducted Type (E1 Type)

3-25. Required Minimum Space for Installation and
)
Service (73, 106, 140 Types
This air conditioner is usually installed above the ceiling so
that the indoor unit and ducts are not visible. Only the air
intake and air outlet ports are visible from below.
The minimum space for installation and service is shown in
Fig. 3-69.
It is recommended that space be provided (600 × 600 mm)
for checking and servicing the electrical system.
Fig. 3-70 and Table 3-3 show the detailed dimensions of the
indoor unit.
980 (Suspension bolt pitch)
15
620
500
70
35
10
10
Min. 600
500
(Space for service)
130
290
940
Suspension
bolt pitch
980
Suspension
Air suction side
bolt pitch
Refrigerant tubing
Electrical
component
Min. 600
Inspection access
box
Space for
(600 × 600)
service
Min.
(73 Type)
550
or
Min.
(106, 140 Types)
580
Drain pan
Ceiling face
Min. 130
940
793
7 100=700
22 - ø3.2
55
20
(Hole for full
40
circumference)
90
60
48
Electrical component box
4-ø20 hole for
suspension bolt
46
16 - ø3.2
Table 3-3
Unit: mm
(Hole for full
circumference)
Length
4 100=400
A
B
C
Type
500
73, 106
420 395
68
15
140
450 425
98
Refrigerant liquid line (ø9.52 or ø6.35)
Refrigerant gas line (ø19.05 or ø15.88)
Power supply entry
Drain connection (25A, O.D. 32 mm)
1010
Duct connection for suction
Duct connection for discharge
940
35
Drain pan
27
3-26. Required Minimum Space for Installation and
Service (224, 280 Types)
This air conditioner is usually installed above the ceiling so
that the indoor unit and ducts are not visible. Only the air
intake and air outlet ports are visible from below.
The minimum space for installation and service is shown in
Fig. 3-71.
It is recommended that space be provided (600 × 600 mm)
for checking and servicing the electrical system.
Fig. 3-72 shows the detailed dimensions of the indoor unit.
Unit: mm
Fig. 3-69
479
300
41
100
100 5 0
23
178
2
100 100
60
320
43
Unit: mm
Fig. 3-70
1170
Min. 600
(Suspension bolt pitch)
(Space for
1100
service)
Air suction
side
Min. 700
(Space for
Refrigerant
service)
tubing
Min. 610
Min. 130 Drain port
Refrigerant tubing joint (liquid tube ø12.7 mm)
Refrigerant tubing joint (gas tube ø28.6 mm)
Power supply outlet
Drain port (O.D. 32 mm)
Duct connection for suction
Duct connection for discharge
1310
1070
10 100P=1000
106
44
28-ø3.5 (Holes all around)
26-ø3.5 (Holes all around)
4 - 37×12
9 100P=900
(Hole for suspension bolt)
964
67
1200 (Suspension bolt pitch)
67
1310
42
364
(236)
364
1334
1428
28
Inspection
Electrical
access
component box
(600 × 600)
Drain pan
Ceiling face
Unit: mm
Fig. 3-71
Unit: mm
Fig. 3-72