ABB EOH Série Boletín De Instrucciones página 17

Ocultar thumbs Ver también para EOH Série:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation
Neutral assembly
Neutral assembly EOHXSN13
Neutral bus is included/factory mounted in service disconnects
EOH361/2/3NJK/NRK/NS/NSS -types and optional in
EOH361/2/3JK/RK/S/SS -types. Install the neutral bus to the
bottom plate of the safety switch to the existing threaded holes
according to the picture. See chapter Cabling.
Wire range: #14 - 2/0, 2.5 - 70 mm
Safety
Torque: wire tightening
switch
Copper
size
[A]
[lbs.in]
[Nm]
30
35
3.9
60
45
5.1
100
50
5.6
2
Aluminium
[lbs.in]
[Nm]
40
4.5
45
5.1
50
5.6
Instruction Bulletin EOH361/2/3JK/RK/S/SS/NJK/NRK/NS/NSS, 1SCC340030M1402 / B | Installation 1/13
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
See general safety instructions on page 1/2 before proceeding.
Failure to follow these instructions will result in death or serious injury.
1