Gewiss Chorus EIB GW 10 793 Manual Del Usuario página 53

Ocultar thumbs Ver también para Chorus EIB GW 10 793:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

OPERATING INSTRUCTIONS
P08 - Minimum percentage value to send the command
When the P08 code appears on the screen, set the
percentage resolution to send the command to the thermal
regulation control device.
The values available are as follows: 5%, 10%, 20%.
Press the
Move on to NOTE 1.
P09 - Setting the regulation differential for 2 point
control
When the
differential time using the
Press the
The regulation differential is the deviance between the set-
point setting and the actual activation temperature. It is
possible to set different regulation differentials for the
heating and air-conditioning functions. It is recommended
to retain the preset values except in special situations.
P10 - Speed 1 regulation differential value
When the P10 appears on the display, set the differential
regulation value to speed V1.
Possible values: from 0.2 °C to 2 °C with a pitch of 0.1
°C.
Press the
P11 - Speed 2 regulation differential value
When the P11appears on the display, set the differential
regulation value to speed V2.
Possible values: from 0.2 °C to 2 °C with a pitch of 0.1
°C.
Press the
This parameter is significant if the number of fan coil stage
set by ETS is greater than 1.
key within 30 seconds to confirm the value set.
symbol appears, set the regulation
keys.
key within 30 seconds to confirm the value set.
key within 30 seconds to confirm the value set.
key within 30 seconds to confirm the value set.
53
E
N
G
L
I
S
H

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Chorus eib gw 14 793

Tabla de contenido