USER INSTRUCTIONS
P12 - Sending day/time to the slave devices
When the P12 code appears on the screen, it is possible
to define when the timer-thermostat should send the date
and time to align these parameters in the slave devices.
(00 = the message is never sent, 01 = the message is
only sent when the power supply returns, 02 = the
message is only sent when the set time changes, 03
= the message is sent when the power supply returns
or when the set time changes, 04 = the message is
sent when the power supply returns, when the set
time changes and at the frequency indicated in P13).
Press the
key within 30 seconds to confirm the value
set.
If the 04 option has been selected, move on to point P13,
otherwise move on to point P14.
P13 - Day/time sending period
When the P13 code appears on the screen, it is possible
to set the sending period for the date and time to align
these parameters in the slave devices etc.
(00 = every 6 hours, 01 = every 12 hours, 02 = every
24 hours, 03 = every week).
Press the
key within 30 seconds to confirm the value
set.
P14 - Sending the PARTY command to the slave devices
When the P14 code appears on the screen, it is possible
to use the
extension of the PARTY command to the slave devices to
the timer-thermostat.
Press the
key within 30 seconds to confirm the value
set.
54
keys to enable (ON) or disable (OFF) the