LERBAKKEN 10, 8410 ROENDE DENMARK
Module 9116B1
Terminal 51-52, 51-53
Ui, Vmax
30 V
Ii, Imax
120 mA
Pi
900 mW
Ci
3 nF
Li
1 μH
Module 9116B1
Terminal 51-54, 52-54
Uo, Voc
28 V
IIC or A,B
Io, Isc
93 mA
IIB or C,E,F
Po
650 mW
IIA or D,G
Module 9116B1
Terminal 51-53
Uo, Voc
28 V
IIC or A,B
Io, Isc
1.1 mA
IIB or C,E,F
Po
8 mW
IIA or D,G
Module 9116B1
Terminal 51-52
Uo, Voc
8.3 V
IIC or A,B
Io, Isc
0.2 mA
IIB or C,E,F
Po
0.4 mW
IIA or D,G
Module 9116B1
Terminal 41,42,43,44
Uo, Voc
8.3 V
IIC or A,B
Io, Isc
13.1 mA
IIB or C,E,F
Po
27.3 mW
IIA or D,G
Installation notes:
The installation and wiring shall be in accordance with the Canadian Electrical Code for Canada and
National Electrical Code NFPA 70, Article 500 or 505 for installation in USA.
The module must be supplied from a Power Supply having double or reinforced insulation.
The use of stranded wires is not permitted for mains wiring except when wires are fitted with cable ends.
For installation on the 9400 Power Rail the power must be supplied from Power Control Module Unit 9410.
Install in pollution degree 2 or better, overvoltage category I or II.
The module must be installed in an enclosure suitable for the environment for which it is used.
In Class I, Division 2 /Zone 2 installations, the subject equipment shall be mounted within a tool-secured
enclosure which is capable of accepting one or more of the Class I, Division 2 wiring methods specified in
the National Electrical Code for USA or the Canadian Electrical Code for Canada
The module is galvanic isolated and does not require grounding.
Use 60 / 75 ºC Copper Conductors with wire Size AWG: (26-14).
Warning: Substitution of components may impair intrinsic safety.
Warning: To prevent ignition of the explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
Warning: Do not mount or remove modules from the Power Rail when an explosive gas mixture is present.
Revision date:
2012-06-08
42
Group
Co
Lo
80 nF
4 mH
640 nF
16 mH 218 μH/Ω
2.1 μF
32 mH 436 μH/Ω
Group
Co
Lo
80 nF 1000 mH
640 nF 1000 mH 17 mH/Ω
2.1 μF 1000 mH 35 mH/Ω
Group
Co
Lo
7 μF 1000 mH 100 mH/Ω
73 μF 1000 mH 400 mH/Ω
1000 μF 1000 mH 800 mH/Ω
Group
Co
Lo
7 μF
207 mH
73 μF
828 mH
1000 μF 1000 mH 10 mH/Ω
Version Revision
V6 R0
9116 - Product Version 9116-003
Module 9116B2
Terminal 51-52, 51-53
Ui, Vmax
30 V
Ii, Imax
120 mA
Pi
900 mW
Ci
3 nF
Li
1 μH
Module 9116B2
Lo/Ro
Terminal 51-54, 52-54
54 μH/Ω
Uo, Voc
21.4 V
Io, Isc
93 mA
Po
650 mW
Module 9116B2
Lo/Ro
Terminal 51-53
4 mH/Ω
Uo, Voc
21.4 V
Io, Isc
1.1 mA
Po
8 mW
Module 9116B2
Lo/Ro
Terminal 51-52
Uo, Voc
8.3 V
Io, Isc
0.2 mA
Po
0.4 mW
Module 9116B2
Lo/Ro
Terminal 41,42,43,44
1 mH/Ω
Uo, Voc
8.3 V
5 mH/Ω
Io, Isc
13.1 mA
Po
27.3 mW
Prepared by:
9116QF01
Group
Co
Lo
0.16 μF
4 mH
IIC or A,B
1.13 μF
16 mH 218 μH/Ω
IIB or C,E,F
4.15 μF
32 mH 436 μH/Ω
IIA or D,G
Group
Co
Lo
0.16 μF 1000 mH
IIC or A,B
1.13 μF 1000 mH 17 mH/Ω
IIB or C,E,F
4.15 μF 1000 mH 35 mH/Ω
IIA or D,G
Group
Co
Lo
7 μF 1000 mH 100 mH/Ω
IIC or A,B
73 μF 1000 mH 400 mH/Ω
IIB or C,E,F
1000 μF 1000 mH 800 mH/Ω
IIA or D,G
Group
Co
Lo
7 μF
207 mH
IIC or A,B
73 μF
828 mH
IIB or C,E,F
1000 μF 1000 mH 10 mH/Ω
IIA or D,G
PB
Lo/Ro
54 μH/Ω
Lo/Ro
4 mH/Ω
Lo/Ro
Lo/Ro
1 mH/Ω
5 mH/Ω
Page:
2/4