9116 Universal converter
CONNEC
Selected sensor connection type for RTD or linear resistance
measurements (for SENSOR = Ni or Pt or IN.TYPE = LIN.R):
2W = 2-wire
3W = 3-wire
4W = 4-wire
If 2W or 3W is selected, the end user must ensure that the
applied sensor wiring does not introduce failures exceeding the
requirements for the safety application.
R 0%
0% input range for linear resistance measurements
(for IN.TYPE = LIN.R).
This value must be < (R 100% - minimum span), refer to 4.2.1
R 100%
100% input range for linear resistance measurements
(for IN.TYPE = LIN.R)
This value must be > (R 0% + minimum span), refer to 4.2.1
UNIT
Selected temperature unit for IN.TYPE = TEMP
°C = degrees Celsius
°F = degrees Fahrenheit
For IN.TYPE ≠ TEMP selectable units refer to routing diagram
DISP.LO
0% display value on 4501. Can be used as base for relay
setpoints (for IN.TYPE ≠ TEMP)
DISP.HI
100% display value on 4501. Can be used as base for relay
setpoints (for IN.TYPE ≠ TEMP)
NEW.PAS
Password for protection of the device configuration from
unauthorized access. Range from 0 to 9999.
Version No. V3R0
safety Manual
13