2. Features
IEC 309P AC Input Power Cord(PDUMNH32HV): The cord
is permanently attached to the PDU and has a 2P + E IEC
309P plug.
L6-30P AC Input Power Cord (PDUMNH30HV): The cord is
permanently attached to the PDU and has a NEMA L6-30P
plug.
AC Input Power Cord (PDUMNH20HV): The detachable
cord has an IEC-320-C19 connector
and an IEC-320-C20
A
connector
.
B
A
B
IEC-320-C20 Power Inlet (PDUMNH20HV): The IEC power
inlet connects to the included power cord or a compatible
user-supplied power cord.
AC Input Adapter (PDUMNH20HV): The adapter converts
the AC input power cord to a NEMA L6-20P plug. The
included retention bracket (not shown) secures the
connection.
IEC-320-C13 Output Receptacles: These receptacles
distribute 208/230V AC power to connected equipment.
IEC-320-C19 Output Receptacles (PDUMNH30HV &
PDUMNH32HV): These receptacles distribute 208/230V AC
power to connected equipment.
Digital Load Meter (Ammeter) (PDUMNH20HV): The digital
load meter displays the load in amps.
LOAD (AMPS)
WEBCARDLX: Allows you to operate this PDU as a managed
network device, accessible via SNMP network management
STATUS CONFIG
RESET
platform, web browser, SSH or Telnet.
3
16-11-159-933684.indb 3
1/3/2017 3:57:51 PM